Vermont Castings Encore 2044-CAT-C Installation Manual Download Page 20

Vermont Castings  •  Encore Model 2040-CAT-C Installation Manual_R3  •  2019 - ___ •  09/20

20

8390-204i

Figure 5.13

 - Floor Installation

Fire Risk

Asphyxiation Risk

Do not draw outside combustion air from:

•  Wall, floor or ceiling cavity

•  Enclosed space such as an attic or garage

•  Close proximity to exhaust vents or chimneys

Fumes or odor may result

WARNING

!

Asphyxiation Risk

Outside  air  inlet  must  be  located  to  prevent 

blockage from:

WARNING

!

•  Leaves 

•  Snow or ice 

•  Other debris

Blockage may cause combustion air starvation

Smoke  spillage  may  set  off  alarms  or  irritate  sensitive 

individuals.

Asphyxiation Risk

Length  of  outside  air  supply  duct  shall  NOT 

exceed the length of the vertical height of the 

exhaust flue.

WARNING

!

•  

Fire will not burn properly

   Smoke spillage occurs when door is opened due to 

air starvation

L. Smoke and CO Detectors & Safety Tips

Smoke and CO Detectors

The  use  of  smoke  and  carbon  monoxide  (CO)  detectors 

throughout the home is strongly advised, even if not 

required by building codes or insurance regulations. 

It  is  a  good  idea  to  install  a  smoke  detector  in  the  living 

areas  and  each  bedroom.  Follow  the  smoke/CO  detector 

manufactures placement and installation instructions and 

maintain regularly.

You  may  not,  however,  wish  to  install  a  detector  in  the 

immediate vicinity of the stove. Depending on the sensitivity 

of the unit, the alarm can be set off while you are tending 

the fire or emptying the ashes. If you install a detector in the 

same room, locate it as far away from the stove as possible.

Safety Tips

Conveniently locate a “Class A” fire extinguisher to contend 

with  small  fires.  Be  sure  the  fire  extinguisher  works  and 

is clearly visible. All occupants of the house should know 

where it is, and how it operates. Have heavy stove gloves 

available near the stove. Have special safety accessories 

(e.g., Child Guard Screen) available for use if small children 

will be in the home.

In the event of a stove pipe or chimney fire….
•  Evacuate the house immediately
•  Notify the fire department
•  If the fire isn’t too threatening, closing down the stove 

tight, (damper, primary air, all doors) will help to smother 

the fire.

•  Inspect  your  stove,  vent  pipe  and  chimney  for  any 

damage  caused  by  the  fire  and  correct  any  damage 

before using your stove again.

Fire Risk

•  Do not leave the fire unattended when the 

door  is  unlatched  or  when  using  the  fire 

screen.

•  Unstable firewood could fall out of the firebox 

creating a fire hazard to your home.

WARNING

!

Summary of Contents for Encore 2044-CAT-C

Page 1: ...ce Do not over fire If appliance or chimney connector glows you are over firing Over firing will void your warranty Comply with all minimum clearances to combustibles as specified Failure to comply may cause house fire Installation and service of this appliance should be performed by qualified personnel Hearth Home Technologies recommends HHT Factory Trained or NFI certified professionals HOT SURF...

Page 2: ... and Installation Considerations 5 B Fire Safety 5 C Negative Pressure 5 D Tools And Supplies Needed 6 E Inspect Appliance and Components 6 F Install Checklist 7 3 Dimensions and Clearances A Appliance Dimensions 8 B Hearth Protection Requirements 9 C Clearances to Combustibles 10 D Locating Your Appliance Chimney 11 E Chimney Termination Requirements 11 F Chimney Location 2 10 3 Rule 12 4 Chimney...

Page 3: ...it must be bolted to the floor This can be done using an appropriate fastener for the application The appliance must be properly grounded to the frame of the mobile home with 8 copper ground wire and chimney must be listed to UL103 HT or a listed UL 1777 full length six 152mm diameter liner must be used Mobile Home Bracket Kit 0003264 must be installed in a mobile home installation D Glass Specifi...

Page 4: ... or surfaced with any of the following materials Wood Compressed Paper Plant Fibers Plastic Plywood OSB Sheet Rock drywall Any material that can ignite and burn flame proofed or not plastered or non plastered NOTE This installation must conform with local codes In the absence of local codes you must comply with the UL1482 11 UL 737 11 UM 84 HUD and NPFA211 in the U S A and the ULC S627 00 and CAN ...

Page 5: ...ing should be given serious consideration 1 Install at least one smoke detector on each floor of your home to ensure your safety They should be located away from the heating appliance and close to the sleeping areas Follow the smoke detector manufacturer s placement and installation instructions and be sure to maintain regularly 2 2 Getting Started Check building codes prior to installation Instal...

Page 6: ...ed duct work and air handler joints and seams taped or sealed Basement installations should be avoided Reciprocating saw Framing material Pliers High temp caulking material Hammer Gloves Phillips screwdriver Framing square Flat blade screwdriver Electric drill and bits Plumb line Safety glasses Level Tape measure Misc screws and nails 1 2 3 4 in length 6 or 8 self drilling screws Installation and ...

Page 7: ...ocked and secured in place with proper clearance Chimney meets recommended height requirements 16 Feet Roof flashing installed and sealed Terminations installed and sealed Clearances Combustible materials not installed on non combustible areas Verified all clearances meet installation manual requirements Mantels and wall projections comply with installation manual requirements Protective hearth st...

Page 8: ...65 mm 15 1 2 394 mm 5 127 mm 2 7 8 73 mm 23 3 4 603 mm 15 381 mm Door opening width 19 7 8 505 mm Figure 3 3 Top View 5295 Encore 2N1 dimensions 1 3 4 44 mm 3 3 4 95 mm 16 7 8 429 mm 25 635 mm Top exit flue collar height 27 686 mm 25 3 4 654 mm 18 1 2 470 mm 7 1 4 184 mm 27 686 mm 22 3 4 578 mm Flue Centerline to glass surface Door opening width 19 7 8 505 mm Figure 3 2 Side View 5295 Encore 2N1 d...

Page 9: ...ctions must extend beneath the flue pipe when installed with horizontal venting and extend 2 51 mm beyond each side Figure 3 7 39 1 4 in minimum 44 in minimum 16 in FRONT DOOR OPENING 6 in USA 6 in Figure 3 5 Fire Risk Hearth pads must be installed exactly as specified High temperatures or hot embers may ignite concealed combustibles WARNING Figure 3 6 67 1 2 in 40 in 22 in 55 1 2 in 16 in front d...

Page 10: ...9 1 2 Fire Risk Comply with all minimum clearances to combustibles as specified Failure to comply may cause house fire WARNING 21 533 mm Mantel 12 Max 53 1346 mm Horizontal Through Wall Top and Side View D B C G H Appliance to Ceiling Clearance Figure 3 10 Fireplace and Mantel Trim Clearances Unprotected NFPA 211 Protected A Mantel Trim 28 711 mm 15 381 mm B Top Trim 25 635 mm 15 381 mm C Side Tri...

Page 11: ...e chimney should Install through the warm space enclosed by the building envelope This helps to produce more draft especially during lighting and die down of the fire Penetrate the highest part of the roof This minimizes the affects of wind turbulence and down drafts NOTICE Locating the appliance in a basement or in a location of considerable air movement can cause intermittent smoke spillage from...

Page 12: ...ing the diameter of the chimney can affect draft and cause poor performance It is not recommended to use offsets and elbows at altitudes above 4000 feet above sea level and or when there are other factors that affect flue draft 3 ft 91 cm Minimum Less than 10 ft 305 cm 2 ft 61 cm 3 ft 91 cm Minimum 10 ft 305 cm To Nearest Roofline 2 ft 61 cm Pitched Roof Figure 3 13 10 ft 305 cm or more 3 ft 91 cm...

Page 13: ...rformance of the stove suffers Imagine a vacuum cleaner with a hole in the hose to understand the effecthere Insomecasestheotherappliance canevencause a negative draft through the stove and result in a dangerous draft reversal Chimney Height The common wisdom tells us that a taller flue draws better than a short one A rule of thumb for minimum height states that the total system height from the fl...

Page 14: ...neys Chimney The chimney can be new or existing masonry or prefabricated and must meet the following minimum requirements specified in Section 4C C Chimney Systems Prefabricated Metal Chimney Must be minimum 6 152 mm diameter ID high temperature chimney listed to UL 103 HT 2100 F or ULC S629M Must use components required by the manufacturer for installation Must maintain clearances required by the...

Page 15: ...ng lumber to fit into wall opening Inside opening of frame should be no less than 14 x 14 356 mm x 356 mm Figure 4 4 Attach the wall spacer to the chimney side of the frame 5 Nail the frame into the wall opening The spacer should be on the chimney side 6 Insert the section of the solid insulated chimney into the outer wall of the masonry chimney 7 Tightly secure the length of the solid insulated c...

Page 16: ... be 6 152mm UL103 HT WARNING WARNING Asphyxiation Risk DO NOT CONNECT THIS Appliance TO A CHIMNEY FLUE SERVICING ANOTHER APPLIANCE DO NOT CONNECT TO ANY AIR DISTRIBUTION DUCT OR SYSTEM May allow flue gases to enter the house Improper installation adjustment alteration service or maintenance can cause injury or property damage Refer to the owner s information manual provided with this appliance For...

Page 17: ... get hot Store the handle in the handle holder installed behind the right front leg Figure 5 4 CAUTION Overtightening can strip tapped threads Figure 5 1 Remove unit from shipping brackets 1 4 20 Bolt A Setting up your Stove Remove the unit from the shipping brackets by removing 2 1 4 20 hex head bolts from each shipping bracket leaving brackets attached to the skid Figure 5 1 Save the 1 4 20 hex ...

Page 18: ...he adjustment E Reverse Flue Collar If necessary Remove the 4 sheet metal screws that hold the flue collar heat shield in place Once heat shield is removed remove the 2 screws that attach the flue collar to the back of the stove Figure 5 6 Be sure the gasket around the flue collar opening is in position when you screw the collar back onto the stove Figure 5 7 1 4 1 8 Bracket mounting screw hole lo...

Page 19: ...the fire must be replaced Air is replaced via air leakage around windows and under doors In homes that have tightly sealed doors and windows an outside air source is needed An optional Outside Air Kit is available Items Needed for Installation not supplied Phillips head screw driver Outside air shield Wire ties Plastic outside air vent Flex Rigid pipe Silicone sealant Drills and saws necessary for...

Page 20: ... CO detector manufactures placement and installation instructions and maintain regularly You may not however wish to install a detector in the immediate vicinity of the stove Depending on the sensitivity of the unit the alarm can be set off while you are tending the fire or emptying the ashes If you install a detector in the same room locate it as far away from the stove as possible Safety Tips Co...

Page 21: ...he serial number label on the back of the stove for clearances to combustibles 6 Floor protection requirements must be followed precisely Refer to the Floor Protection section in this manual 7 In Canada this appliance must be connected to a 6 inch 152 mm factory built chimney conforming to CAN ULC 629M STANDARD FOR FACTORY BUILT CHIMNEYS Refer to the Floor Protection section in this manual 8 Use s...

Page 22: ... Important operating and maintenance instructions included Leave this manual with party responsible for use and operation Read understand and followtheseinstructions for safe installation and operation DO NOT DISCARD This product may be covered by one or more of the following patents United States 5341794 5263471 6688302 7216645 7047962 or other U S and foreign patents pending We recommend that yo...

Reviews: