32
VCG Designer Series • DSR36 Installation Manual • 4012-130 • Rev A • 02/20/15
D. Mantel and Wall Projections
A combustible mantel may be positioned no lower than
40 3/8 in. (1026 mm) from the base of the fireplace.
The combustible mantel may have a maximum depth of
12 in. (305 mm) positioned 12 in. (305mm) above the fire
-
place opening. Combustible trim pieces that project no
more than 1 1/2 in. (38 mm) from the face of the fireplace
can be placed no closer than 6 in. (152 mm) from the top of
the opening. Combustible trim must not cover:
• the metal surfaces of the fireplace
• where the non-combustible board is placed over the
metal surfaces
• the space between the metal face of the fireplace and
framing members
Mantel
Combustible Wall
2 x 4 stud wall
Standoffs
Measured from top of fireplace opening
12 in./305 mm
1 1/ 2 in./38 mm
maximum
6 in./152 mm
minimum
12 in./305 mm
minimum
Combustible
Decorative Facing
Non-combustible
Decorative Facing
such as: Steel, iron,
brick, tile, concrete,
slate, glass, plasters
Seal joint with
non-combustible
sealant
7 ft (2134 mm)
minimum
base of fireplace
to ceiling
Grid lines at 1 in. scale
Figure 7.10 Mantel Specifications
WARNING!
Risk of Fire!
Vermont Castings Group is not responsible for
discoloration, cracking or other material failures of
finishing materials due to heat exposure or smoke.
• Choose finishing materials carefully.