Vermont Castings Aspen II 1405C Homeowner'S Installation And Operating Manual Download Page 8

8

Vermont Castings Aspen

®

 II Multi-Fuel

30003892

Always adhere to local building codes when installing a 
wall pass-through.
Figure 7 shows an alternate method of passig a con-
nector through a wall. All combustible material in the 
wall is cut away to provide the required clearance that 
is three times the pipe diameter. The resulting space 
must remain empty. A flush-mounted sheet metal cover 
may be used on one side only. If covers must be used 
on both sides, each cover must be mounted on noncom-
bustible spacers at least 25 mm (1”) clear of the wall.

do Not coNNect aN aSpeN ii multi-fuel to 
aNy air diStributioN duct or SyStem.

ST247

Rear exit floor dgrm

12/14/99   djt

Wood framing requires pro-

tection form radiant heat

ST247

fig. 8 

 Supporting timbers under fireplace hearth are consid-

ered to be combustible.

ST276
CSA approved wall 
pass-through
12/99

Min. 460 mm (18”)

24 ga. Sheet 
Steel Support 
(one side only)

ST276

fig. 7

  An approved wall pass-through.

Chimney clearance to 

sheet steel supports 

and combustibles

Min. 460 mm

(18”)

24 ga. Sheet 

Stee Support

Chimney 

Connector

Masonry Chimney

51 mm (2”) Min.

hearths

This appliance must be installed on to hearth that 
meets the requirements of Part J of the Building Regu-
lations 2000 (Combustion Appliances and Fuel Storage 
Systems). This can be achieved by ensuring that the 
hearth is constructed and sized in accordance with the 
guidelines included in section 2 of approved document 
‘J’. The size and clearances of the hearth are as fol-
lows:
The constructed hearth should be constructed in ac-
cordance with the recommendations in document J, 
and should be of minimum width 840 mm and minimum 
depth 840 mm (if a free standing hearth b) above) or 
a minimum projection of 150 mm from the jamb (if a 
recessed hearth a) above).

floor protection for fireplace installations 

Do not assume your fireplace hearth is completely 
noncombustible.  
Many fireplace hearths do not satisfy the “completely 
noncombustible” requirement because the brick or 
concrete in front of the fireplace opening is supported 
by heavy wood framing as in Figure 8. Because heat 
passes through brick or concrete readily, it can easily  
pass through to the wood. As a result, such fireplace 
hearths can be a fire hazard and are considered a 
combustible floor.  

Keep in mind that many raised hearths will extend 
less than the required clearance from the front of the 
heater when it is installed. In such cases, sufficient 
floor protection as described above must be added in 
front of the hearth to satisfy the minimum floor protector 
requirement from the front of the stove: 406 mm (16”) 
from the front. Fireplace hearths must also offer the 
required protection of 152 mm (6”) on either side. 
Optional 76 mm (3”) short legs may be used only on  
such hearths that meet the width and depth require-
ments outlined previously under “floor protection.”
Hearth rugs do not satisfy the requirements for floor 
protection.  
Fireplace installations also have special clearance 
requirements to the side walls, side decorative trim, and 
fireplace mantle. Refer to the information on  fireplace 
and mantel trim shields in this section. 

keep the Stove a Safe distance 

from Surrounding materials

Specifications herein are primarily related to common 
timberframe construction. Both a stove and its chimney 
connector radiate heat in all directions when operat-
ing, and dangerous overheating of nearby combustible 
materials can occur if they are too close to the heat.  A 
safe installation requires that adequate clearance  be 
maintained between the hot stove and its connector 
and nearby combustibles.
Clearance is the distance between either your stove 
(measured from the back edge of the stove’s top plate) 
or chimney connector, and nearby walls, floors, the 
ceiling, and any other fixed combustible surface.  Your 
stove has special clearance requirements that have 
been established after careful research and testing.  
These clearance requirements must be strictly ob-
served.
In addition, furnishings and other combustible  materials 
must be kept away from the stove as well.  In general, a 
distance of 1220 mm (48”) must be maintained between 

Summary of Contents for Aspen II 1405C

Page 1: ...risk of fire follow the installation instructions Failure to follow instructions may result in property damage bodily injury or even death Contact local building officials about restrictions and inst...

Page 2: ...ove you are making a strong statement for pollution free energy But clean burning depends on both the manufacturer and the operator Please read this manual carefully to understand how to properly oper...

Page 3: ...eated up to 65 sq m 700 sq ft Loading Front or top Chimney connector 152 mm 6 diameter Chimney flue size 152 mm 6 minimum Flue exit position Reversible top or rear Primary air Manual set thermostatica...

Page 4: ...ng those referring to national and European standards need to be com plied with when installing this stove Outside Air In some modern super insulated homes there is not enough air for combustion becau...

Page 5: ...stove to the chimney Connecting Flue Pipes Connector pipes should meet the requirements of the building regulations This can be achieved by the use connecting fluepipes included in the following cate...

Page 6: ...ap tors attaches directly to the chimney or to the chimney s ceiling support package while the bottom of the adap tor is screwed to the chimney connector These adaptors are designed so the top end wil...

Page 7: ...guidelines mentioned above for freestanding installations In addi tion give special consideration to the following points Check the clearance between the stove and the chimney connector and any combu...

Page 8: ...nt because the brick or concrete in front of the fireplace opening is supported by heavy wood framing as in Figure 8 Because heat passes through brick or concrete readily it can easily pass through to...

Page 9: ...lid noncombustible surfaces e g the sides and rear of Inglenook fire openings constructed from solid masonry other than to allow safe access to the controls of the stove For this reason minimum side c...

Page 10: ...levation With Shield a t l e a s t 3 x D at least 1 5 x D at least 1 5 x D Plan Without Shield Plan With Shield Air space of at least 12 mm between noncombustible shield and combustible material Fluep...

Page 11: ...ents from the stove before lifting it to its final position Follow the Grate Removal instructions on Page 21 34 Poker Slicer ST878 Fig 12 Remove poker slicer from its shipping position Install Door Ha...

Page 12: ...ondary combustion occurs in the secondary com bustion chamber in the rear of the firebox The high temperatures attained in this area encourage further burning of the volatile gases in the smoke reduci...

Page 13: ...sed 34 DAMPER CONTROLS Damper Open Damper Closed ST882 Fig 17 Damper positions The Glass Door Panel The glass panel used in the door of this stove features a heat reflective coating on the outside sur...

Page 14: ...or this stove and will give the best output and cleanliness in use As a rough guide hardwoods should be split and stacked and allowed to air dry under cover for 8 18 months depending on the split size...

Page 15: ...s to fall away into the ash pan 5 Add fuel 6 Close the damper and rest the primary air control as soon as the fire is re established With a thick ember bed and well seasoned wood this may be carried o...

Page 16: ...ee any ash deposited on the grate bars Ash Disposal Remove ash before it reaches the top of the ash pan Check the level at least once a day and before each refuelling If the ash level is close to the...

Page 17: ...stove s flue outlet When a chimney Draft Management serves an airtight stove more is not better in fact it can be a disadvantage Hot gases cool off through expansion if we vent a stove with a 152 mm...

Page 18: ...you should open up the damper to let the smoke rise to the flue more quickly let more air into the firebox and avoid big loads of firewood Run your stove with enough primary air so that you always see...

Page 19: ...ion Overtightening can crack the glass immediately or cause it to crack if it is unable to expand when hot Maintenance Let the fire in the stove go out and allow the stove to cool completely before be...

Page 20: ...ss the gasketed part firmly against its normal mating surface to seat the gasket evenly in its ST559 Remove gasket 11 30 00 djt Cement Stove Gasket ST561 Fig 26 Lay a bead of gasket cement then press...

Page 21: ...sote or soot in the fluepipe connector secondary combustion chamber and inte rior of the stove As a general guide if deposits are 3mm or greater in thickness they should be cleaned off using a stiff b...

Page 22: ...Secondary Combustion Chamber Firebricks and Damper Assembly 1 The damper assembly is retained by two tab bolts These must first be loosened from both sides of the upper rear face of the stove 2 When l...

Page 23: ...ifications prices and discontinue colors and products at any time without notice Aspen II Multi Fuel Heater Model 1405CE 3892 Aspen II MF parts 6 07 1 2 3 8 9 12 13 19 10 11 14 14 14 15 17 18 16 21 20...

Page 24: ...ebrick Side 30002200 21 Lower Fireback 30002107 22 Left Vertical Manifold 30002186 23 Front Linkage 30002150 24 Linkage 30002147 25 Label 1601223 26 Grate 30002116 27 Ashpan 30002130 28 Right Vertical...

Page 25: ...l hardware stores Stove Serial No __________________________ Dealer _________________________________ ________________________________________ ________________________________________ Phone __________...

Page 26: ...26 Vermont Castings Aspen II Multi Fuel 30003892...

Page 27: ...ed catalyst Exclusions Limitations 1 This product must be installed or serviced by a qualified installer preferably NFI or WETT Canada certified as prescribed by the local jurisdiction It must be inst...

Page 28: ...MHSC 149 Cleveland Drive Paris Kentucky 40361 www mhsc com...

Reviews: