Recommended Wiring
Wiring
Signal
AWG
Twisted Pair
Conductor
Shielded
Max Length
Reader Option 1
(Wiegand or AD31)
22
Yes
Yes
250ft
Reader Option 2
(Wiegand or AD31)
20
Yes
Yes
300ft
Reader Option 3
(Wiegand or AD31)
18
Yes
Yes
500ft
12V Power (22 Gauge)
22
Yes
Yes
600ft
12V Power (18 Gauge)
18
Yes
Yes
1500ft
Inputs
22
Yes
Yes
1000ft
Dry Relay Output
18
Yes
Yes
1500ft
The AX11 card reader interface is capable of supporting Verkada Readers over RS-485 and standard
Wiegand readers. The following table shows the wire types that are recommended for use with AX11.
We recommend using one twisted pair for GND and Vin (power) and one twisted pair for the data (D0/D1 or
A/B).
Wiring methods shall be in accordance with National Electrical Code, ANSI/NFPA 70.
Required Network Settings
With the AX11, you must use shield wiring.
Drain wire of the cable should be secure to the nearest grounding point, indicated with on the controller,
with a conductive M4 screw.
An Ethernet connection with DHCP must be used to connect the AX11 to the Local Area Network (LAN).
You also need to configure firewall settings to communicate with the AX11.
• TCP port 443
• UDP port 123 (NTP time synchronization)