
Installing the replacement cooling module
Use the following steps to install the replacement cooling module.
To install the replacement cooling module
Caution:
Handle the replacement cooling module carefully to avoid damaging the connector pins.
Do not install a fan module if any pins appear to be bent.
1
Put on a grounded ESD-compliant wrist strap or take other ESD-preventive measures.
2
Remove the replacement cooling module from its packaging.
3
Orient the replacement cooling module so that the black and orange release latch is on the right
side of the module.
4
Slide the replacement cooling module completely into the storage shelf.
A click should be heard as the retaining latch engages.
5
Monitor the cooling module LEDs for any faults.
Verify that the LED on the replacement module is green and that the cooling module is moving
air.
6
If the LED is not green, or if the cooling module is not moving air, contact Veritas Technical
Support.
5
HSP #228 - Replacing a 5U84 Storage Shelf cooling module