background image

6%2)3).$5342)%3

H704

INSTALLATION GUIDE

 Z202366-0M 

page 3 

©2008 Veris Industries   USA 800.354.8556 or 503.598.4564  / [email protected]   

02081

1.  Inspect the Mounting Bracket Kit. The acquisition and interconnection boards are 

mounted to the bracket at the factory.

safety

UL listed under standard 508 as an "open type device."
Installation category:  CAT II or CAT III
Critical components evaluated to UL 1950.

The H704 Series must be installed in as appropriate electrical and fire enclosure per 
local regulations.
For use in a Pollution Degree 2 or better environment only.

A Pollution Degree 2 environment must control conductive pollution and the 
possibility of condensation or high humidity. Consideration must be given to the 
enclosure, the correct use of ventilation, thermal properties of the equipment and 
the relationship with the environment.

This symbol indicates an electrical shock hazard exists.

Documentation must be consulted where this symbol is used 

on the product.

installation

11.375"

(289 mm)

1.12"

(28 mm) 

5.75"

(146 mm)

Data Acquisition Board

Mounting Bracket

Data Acquisition Board

19.5

495

1.0

25

0.75

19

Side View

1.3

33

0.4 opening

10.16

0.75 on center

19

1.2

31

20.31

515

“Right” strip shown

50A Solid-Core CT Strips

19.5"

(241 mm)

0.75" on center

(19 mm)

0.35" opening

(9 mm)

1.0"

(26 mm)

24.0"

0.35" opening

1.0"

1.0" on center

H704-42

H704-42/1

H704-42

H704-42/1

H704-42(H)

100A Solid-Core CT Strip

Shop for Veris products online at:

1.877.766.5412

www.

PowerMeterStore

.com

Summary of Contents for H704-42

Page 1: ...switch selectable 2400 4800 9600 19200 Parity DIP switch selectable NONE ODD EVEN Communication Format 8 data bits 1 start bit 1 stop bit Termination 5 position depluggable connector TX TX SHIELD TX RX TX RX Defaults Warning Register 60 of current sensor max configurable Alarm Register 70 of current sensor max configurable Breaker Size Register 20 A Incaseofacurrentfaultabove60A 120fortheHversion ...

Page 2: ...s network 2 OpticalCommunicationsIsolation Optical isolators are used to separate 120 VAC portions of the circuit from the RS485 network 3 AliveLED Flashes once per second to indicate correct operation If steadily lit or out indicates internal failure 4 50 PinRibbonCableConnectors DataAcquisitionBoard 18 inch 457 mm ribbon cables are provided standard for easy snap connection of current sensor str...

Page 3: ...ution and the possibility of condensation or high humidity Consideration must be given to the enclosure the correct use of ventilation thermal properties of the equipment and the relationship with the environment This symbol indicates an electrical shock hazard exists Documentation must be consulted where this symbol is used on the product Installation 11 375 289 mm 1 12 28 mm 5 75 146 mm Data Acq...

Page 4: ... board 4 Check that CT serial numbers and meter serial numbers match Meter and CT sold as set with accuracy calibrated as a set For208 230VACPowerConnectionversion orderH704 42E H704 42 IE 522 4 3 3 2 342 0 522 4 3 3 2 342 0 522 4 3 3 2 342 0 522 4 3 3 2 342 0 ATA CQUISITION OARD ODBUS 5P TO gS 2IBBON ABLE 4O ONTROLLER OR 0 0ANEL OARD 0ANEL OARD 6 4 2 12 10 8 18 16 14 24 22 20 30 28 26 36 34 32 42...

Page 5: ...connected together in a daisy chain fashion and properly terminated C The Modbus cable should be shielded twisted pair wire such as Belden 1120A The cable must be voltage rated for the installation 2 Wire 4 Wire 1 Connect 2 wire or 4 wire Modbus RS485 daisy chain network wiring WARNING After wiring the Modbus cable remove all scraps of wire or foil shield from the electrical panel This could be DA...

Page 6: ...th a set of 8 dip switches for addressing See below LSB MSB VALUE Example 2 wire9600BaudNoParity DefaultOnly 1 X X X X X X 2 On Off 3 Off On Off On 4 Off Off On On 5 6 7 X X X X X X 8 X X X X X X 2400 Baud 4800 Baud 9600Baud 19200 Baud 2wire 4 wire Wiring Baud Rate Parity Wiring None Even Odd Off Off On Off On Off Parity Baud Rate DESIRED RESULT Switch Baud Rate and Parity Switch Setttings 40 2 Ad...

Page 7: ...upport veris com 02081 communications setup DO NOT USE ZERO 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 Shop for Veris products online at 1 877 766 5412 www PowerMeterStore com ...

Page 8: ...8 series or equivalent 5 Reconnect 120V to Data Acquisition Board 6 Reconnect power to panel 7 Check Alive LED for proper function See Product Diagram section for location service ACCESSORIES CBL008 Cable Ribbon 18 in 457 mm BCM CBL016 Cable Ribbon 48 in 1219 mm BCM CBL017 Cable Ribbon 60 in 1524 mm BCM CBL018 Cable Ribbon 72 in 1829 mm BCM CBL019 Cable Ribbon 97 in 2464 mm BCM CBL020 Cable Ribbon...

Reviews: