INSTALLATION GUIDE

 Z202366-0M 

page 2 

©2008 Veris Industries   USA 800.354.8556 or 503.598.4564  / [email protected]   

02081

operation

product diagram

dimensions

Circuit Board and Mounting Bracket

The H704-42 Branch Current Monitor is a current sensing device designed to monitor 
all 42 poles of a panel board. Designed for critical load monitoring such as Co-location 
Data Centers and lighting panels, the H704-42 provides important branch circuit 
amperage and capacity information. By reporting current levels and initiating 
capacity warnings and alarms, the H704-42 allows the management of power and 
eliminates open circuits caused by overloaded breakers.

The H704-42 consists of a Data Acquisition Board and two 21-unit current sensor 
strips. The strips are mounted on each side of the panel board along the termination 
points of each breaker. The conductor passes through the appropriate current sensor 
before terminating at the breaker. Each strip transmits the current data to the Data 
Acquisition Board through snap on ribbon cable. An optional hardware kit is available 
for mounting the H704-42.

Data is transmitted using an RS485 Modbus protocol. Each Data Acquisition Board is 
addressed on the modbus daisy chain network.

Setup is made easy with a PC based configuration tool which allows for global or 
individual selection of breaker size, warning levels, and alarm levels.

*For 208/230VAC Power Connection version, order H704-42(H)(E)/H704-42/1(H)(E)

1.  

RS 485 2 or 4-Wire Connection:

  Daisy chain multiple H704-42's using a 2-wire 

or 4-wire modbus network.   

2.  

Optical Communications Isolation:  

Optical isolators are used to separate 120 

VAC portions of the circuit from the RS485 network.

 3.  

Alive LED:

  Flashes once per second to indicate correct  operation. If steadily lit or 

out, indicates internal failure.

 4.  

50-Pin Ribbon Cable Connectors (Data Acquisition Board):

  18-inch (457 mm) 

ribbon cables are provided standard** for easy snap connection of current sensor 
strips to this point of the Data Acquisition Board.

5.  

Control (Mains) Power Connection*:

  Easy 2-wire 120 VAC line to neutral 50/60 

Hz.

6.  

250VAC 100mA Time Delay Fuse:

  Fused power connection for circuit protection.

7.  

Power Transformers:

  Linear power supply for reliability and low noise

8.  

Baud Rate & Parity Selection Switches:

  Field selectable RS-485 serial interface 

control.

9.  

Modbus Address Dip Switches:

  Each Modbus device must have a unique 

address. These switches must be set to assign an individual address before the 
device is connected to the network.   

10.  

TX LED:

  Indicates successful transmission of information over the Modbus 

network.

11.  

RX LED:

  Indicates data received on the Modbus network

12.  

Current Sensors:

  Each current sensor is capable of monitoring conductors 

carrying up to a maximum of 50 amps. Maximum wire size capacity is #6 AWG 
THHN. H version can monitor up to 100 amps with a maximum wire size capacity 
of #2 AWG THHN

13.  

50 Pin Ribbon Cable Connectors (CT Strips):

  18" ribbon cables are provided 

standard** for easy snap connection of Data Acquisition Board strips to this point 
of the current sensor strips 

*For 208/230VAC Power Connection version, order catalog number H704-42/H704-42/1E.

**Additional sizes are available for sale.

12 

10 

18 

16 

14 

24 

22 

20 

30 

28 

26 

36 

34 

32 

42 

40 

38 

10

11

13

12

Shop for Veris products online at:

1.877.766.5412

www.

PowerMeterStore

.com

Summary of Contents for H704-42

Page 1: ...switch selectable 2400 4800 9600 19200 Parity DIP switch selectable NONE ODD EVEN Communication Format 8 data bits 1 start bit 1 stop bit Termination 5 position depluggable connector TX TX SHIELD TX RX TX RX Defaults Warning Register 60 of current sensor max configurable Alarm Register 70 of current sensor max configurable Breaker Size Register 20 A Incaseofacurrentfaultabove60A 120fortheHversion ...

Page 2: ...s network 2 OpticalCommunicationsIsolation Optical isolators are used to separate 120 VAC portions of the circuit from the RS485 network 3 AliveLED Flashes once per second to indicate correct operation If steadily lit or out indicates internal failure 4 50 PinRibbonCableConnectors DataAcquisitionBoard 18 inch 457 mm ribbon cables are provided standard for easy snap connection of current sensor str...

Page 3: ...ution and the possibility of condensation or high humidity Consideration must be given to the enclosure the correct use of ventilation thermal properties of the equipment and the relationship with the environment This symbol indicates an electrical shock hazard exists Documentation must be consulted where this symbol is used on the product Installation 11 375 289 mm 1 12 28 mm 5 75 146 mm Data Acq...

Page 4: ... board 4 Check that CT serial numbers and meter serial numbers match Meter and CT sold as set with accuracy calibrated as a set For208 230VACPowerConnectionversion orderH704 42E H704 42 IE 522 4 3 3 2 342 0 522 4 3 3 2 342 0 522 4 3 3 2 342 0 522 4 3 3 2 342 0 ATA CQUISITION OARD ODBUS 5P TO gS 2IBBON ABLE 4O ONTROLLER OR 0 0ANEL OARD 0ANEL OARD 6 4 2 12 10 8 18 16 14 24 22 20 30 28 26 36 34 32 42...

Page 5: ...connected together in a daisy chain fashion and properly terminated C The Modbus cable should be shielded twisted pair wire such as Belden 1120A The cable must be voltage rated for the installation 2 Wire 4 Wire 1 Connect 2 wire or 4 wire Modbus RS485 daisy chain network wiring WARNING After wiring the Modbus cable remove all scraps of wire or foil shield from the electrical panel This could be DA...

Page 6: ...th a set of 8 dip switches for addressing See below LSB MSB VALUE Example 2 wire9600BaudNoParity DefaultOnly 1 X X X X X X 2 On Off 3 Off On Off On 4 Off Off On On 5 6 7 X X X X X X 8 X X X X X X 2400 Baud 4800 Baud 9600Baud 19200 Baud 2wire 4 wire Wiring Baud Rate Parity Wiring None Even Odd Off Off On Off On Off Parity Baud Rate DESIRED RESULT Switch Baud Rate and Parity Switch Setttings 40 2 Ad...

Page 7: ...upport veris com 02081 communications setup DO NOT USE ZERO 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 Shop for Veris products online at 1 877 766 5412 www PowerMeterStore com ...

Page 8: ...8 series or equivalent 5 Reconnect 120V to Data Acquisition Board 6 Reconnect power to panel 7 Check Alive LED for proper function See Product Diagram section for location service ACCESSORIES CBL008 Cable Ribbon 18 in 457 mm BCM CBL016 Cable Ribbon 48 in 1219 mm BCM CBL017 Cable Ribbon 60 in 1524 mm BCM CBL018 Cable Ribbon 72 in 1829 mm BCM CBL019 Cable Ribbon 97 in 2464 mm BCM CBL020 Cable Ribbon...

Reviews: