Installation Guide

Air Quality

G Series

TM

For any service or installation, consult qualified service personnel. To ensure continued reliable operation, replace the sensor 
module every five years with a Veris Industries CO sensor replacement module (Veris part number AA09). 

Replacement instructions:

1.  Disconnect power from the unit.

2.  Carefully remove the old sensor module.

3.  Install the new module firmly into the socket.

4.  Reconnect power to the unit.

5.  The replacement sensor requires 96 hours to stabilize after initial power application.

The sensor module is factory calibrated. No field calibration is required or possible. Verify proper operation by observing the LED 
indicators.

Problem

Solution

4-20 mA output does not function

• Verify that the unit is a 4-20 model.
• Verify that the unit is wired for sourcing output.

Output is half or twice what is 

expected

• Verify span jumper is set to desired scale.
• For voltage units, verify jumper is set to desired 

voltage output scale.

Output is inaccurate or unstable

• Allow 96 hours for sensor to burn in and stabilize.

Service

Troubleshooting