6%2)3).$5342)%3

H8186-CB

INSTALLATION GUIDE

Z204062-0E 

page 7 

©2008 Veris Industries   USA 800.354.8556 or 503.598.4564  / [email protected] 

 

06081

BACnet Object 

Description 

Description Field 

Units              

Device Object: 

This device 

Veris H81xx Energy  

N/A 

 

 

Meter with H8186-CB 

 

 

BACnet Communications Board 

 
Analog Value Object 1: 

Accumulated Energy  

kWh_Total 

kWh

Analog Value Object 2: 

Device Instance 

Device_Instance 

N/A

Analog Input Object 1: 

Total Real Power    

kW_Total 

kW

Analog Input Object 2: 

Total Reactive Power 

kVAR_Total 

kW

Analog Input Object 3: 

Total Apparent Power 

kVA_Total 

kW

Analog Input Object 4: 

Total Power Factor 

PF_Total 

Unitless

Analog Input Object 5: 

Average Line-Line Voltage 

Volts_LL_Avg 

VOLTS

Analog Input Object 6: 

Average Line-Nuetral Voltage  Volts_LN_Avg 

VOLTS

Analog Input Object 7: 

Average Current 

Current_Avg 

AMPS

Analog Input Object 8: 

Real Power: Phase A 

kW_A 

kW

Analog Input Object 9: 

Real Power: Phase B 

kW_B 

kW

Analog Input Object 10: 

Real Power: Phase C 

kW_C 

kW

Analog Input Object 11: 

Power Factor: Phase A 

PF_A 

Unitless

Analog Input Object 12: 

Power Factor: Phase B 

PF_B 

Unitless

Analog Input Object 13: 

Power Factor: Phase C 

PF_C 

Unitless

Analog Input Object 14: 

Voltage: Phase A-Phase B 

Volts_AB 

VOLTS

Analog Input Object 15: 

Voltage: Phase B-Phase C 

Volts_BC 

VOLTS

Analog Input Object 16: 

Voltage: Phase A-Phase C 

Volts_AC 

VOLTS

Analog Input Object 17: 

Voltage: Phase A-Neutral 

Volts_AN 

VOLTS

Analog Input Object 18: 

Voltage: Phase B-Neutral 

Volts_BN 

VOLTS

Analog Input Object 19: 

Voltage: Phase C-Neutral 

Volts_CN 

VOLTS

Analog Input Object 20: 

Current: Phase A 

Current_A 

AMPS

Analog Input Object 21: 

Current: Phase B 

Current_A  

AMPS

Analog Input Object 22: 

Current: Phase C 

Current_A  

AMPS

Clearing the kWhAccumulator:  Clear the kWh accumulator to zero by writing 0.0 to the PRESENT_VALUE property Analog Value Object 1.

Changing the Device_Instance:

 

•  Units are shipped with a default Device Instance of 123.

 There are 2 methods of changing the Device_Instance:

• 

 

1.  Write the Object_Identifier directly.  The Device’s Object_Identifier contains both the Object_Type (Device = 8) and the Object_Instance (0-4194302).  Write the  

 

 

Device’s Object_Identifier with (8,Instance) to change the Device_Instance.

 

2.  Use Analog Value Object 2.  Although a REAL (i.e. floating point) value, writing the Present_Value of AV2 is an alternative method of changing the Device_In 

 

 

 

stance.  This value may be written in the range 0-4194302.  Any fractional value will be truncated (eg. 57.234 will be written as 57).

bacnet descriPtions

Archived Document

Summary of Contents for H8126-CB

Page 1: ...UJPOT 0QFSBUJPO PG UIJT FRVJQNFOU JO B SFTJEFOUJBM BSFB JT MJLFMZ UP DBVTF IBSNGVM JOUFSGFSFODF JO XIJDI DBTF UIF VTFS XJMM CF SFRVJSFE UP DPSSFDU UIF JOUFSGFSFODF BU IJT PXO FYQFOTF PEJmDBUJPOT UP UI...

Page 2: ...for 2 wire or 4 wire communications CAUTION Danger of Explosion if battery is incorrectly replaced Replace only with the same or equivalent type recommended by the manufacturer Dispose of used batteri...

Page 3: ...daisy chain The RS 485 interface will support daisy chains that fall within the specifications shown below Baud Rate Maximum Distances 1 16 Devices 17 32 Devices 9600 10000 ft 3048 m 4000 ft 1219 m 1...

Page 4: ...TX RX TX TX TX SHLD TX RX TX RX TX MASTER SLAVE ON 1 2 3 4 5 6 ON 1 2 3 4 5 6 TX RX RX ALIVE SHLD TX RX TX RX TX TX TX SHLD TX RX TX RX TX TX SHLD RX RX TX TX SHLD TX RX TX RX TX SHIELD RX RX TX TX M...

Page 5: ...TION SLOTS 4 Insert the communication terminal onto the RS 485 communication terminals 5 If the demand subinterval feature is used wire into the end of the demand subinterval terminal 6 Replace the vo...

Page 6: ...Network Address DIP switches for each Network address See Selecting the network Address NETWORK ADDRESS DIP SWITCHES on pages 2 3 for instruction on setting the switches 32 33 34 35 36 37 38 39 40 41...

Page 7: ...Input Object 14 Voltage Phase A Phase B Volts_AB VOLTS Analog Input Object 15 Voltage Phase B Phase C Volts_BC VOLTS Analog Input Object 16 Voltage Phase A Phase C Volts_AC VOLTS Analog Input Object 1...

Page 8: ...t Optional Properties Supported Max_Master Max_Info_Frames Description Location Writable Properties Object_Identifier Max_Master Location Property Range Restrictions Location limited to 64 characters...

Reviews: