Specifications
Sensor Power
Induced from monitored conductor
Insulation Class
600 Vac RMS (UL), 300 Vac RMS (CE)
Amperage Range
0 to 10 A
Frequency
50/60 Hz nominal
Temperature Range
-15 to 60 °C (5 to 140 °F)
Humidity Range
10 to 90% RH, non-condensing
Accuracy
±2% F.S. from 10% to 100% (range)
Response Time
2 seconds
Terminal Block Maximum Wire Size
24 to 14 AWG (0.2 to 2.1 mm
2
)
Terminal Block Torque (nominal)
4 in-lbs (0.45 N-m)
Product Overview
The H623-10 is a current transducer that senses current (amperage) in the 0 to 10 A range. This represents the
maximum current that can be applied to the monitored conductor. The H623-10 transforms the monitored current
into a 0 to 10 Vdc output suitable for connection to building controllers, or other appropriate data acquisition
equipment. The H623-10 requires no external power supply to generate its output.
H623-10
Solid-Core Transducer, 0 to 10 Vdc Output
2.5"
(64 mm)
2.1"
(54 mm)
3.5"
(89 mm)
2.9"
(74 mm)
0.4” x 0.2”
(10 mm x 5 mm)
Slot (2x)
1.2"
(31 mm)
Removable Mounting Bracket
0.7"
(18 mm)
0.5"
(13 mm)
2.1"
(54 mm)
1.0"
(26 mm)
0.6"
(16 mm)
*
* The CE mark indicates RoHS2 compliance. Please refer to the CE Declaration of
Conformity for additional details.
Dimensions
Note: For CE compliance, conductor shall be insulated according to IEC61010-1. The product design provides for basic insulation only. For
applications requiring double or reinforced insulation, please contact the factory.