opEration

The H5004 Remote Status Panel is capable of simultaneously tracking the output 
from up to four separate current transducers and displaying the operation status of 
those conductors in one convenient location. LEDs indicators on the Panel’s face show 
the active status of each conductor. The H5004C Panel Kit includes four H5800 mini 
solid-core transducers, with a range of 1 to 100A. These sensors can be installed up 
to 1000 feet from the H5004 Panel. The H5004 requires 24VAC/DC external power to 
generate its output.

notEs

For load currents less than sensor minimum rating:

 

Wrap the monitored conductor through the center hole and around the sensor body 
to produce multiple turns through the "window." This increases the current measured 
by the transducer.

Controller must be programmed to account for 
the extra turns. e.g., if four turns pass through 
the sensor (as shown) the normal controller 
reading must be divided by 4.

< 1A (sensor min.)

4x

0.5A

DANGER: 5A CTs can present hazardous voltages. 

Install CTs in accordance with manufacturer's instructions. 

Terminate the CT secondary before applying current.

H681x-5A CT

240A

300A:

5A

 4A

> 100A (H5800 max.)

For load currents greater than sensor maximum rating:

 

Use a 5 Amp (H681x series) Current Transformer (CT) as shown.

CAUTION 

RISK OF EQUIPMENT DAMAGE

t %FSBUFUIFQSPEVDUTNBYJNVNDVSSFOUGPSUIFOVNCFSPGUVSOT

UISPVHIUIFTFOTJOHXJOEPXVTJOHUIFGPMMPXJOHGPSNVMB

3BUFE.BY"NQTŸ/VNCFSPG5VSOT.BYNPOJUPSFE"NQT
FH"Ÿ5VSOT"NQTNBYJONPOJUPSFEDPOEVDUPS

t 'BJMVSFUPGPMMPXUIFTFJOTUSVDUJPOTDBOSFTVMUJOPWFSIFBUJOH

BOEQFSNBOFOUFRVJQNFOUEBNBHF

Wiring

Power

24 VAC/DC 

Power Supply

24 VAC/DC IN

_

+

_

+

_

+

_

+

_

+

_

+

_

+

_

+

Sensor 1

Status 1

Output 1

Output 2

Output 3

Output 4

Status 2

Status 3

Status 4

Sensor 2

Sensor 3

Sensor 4

Use Veris H5800 current sensors only.

H5004 Remote Status Panel

Building Control Panel

Digital 

Inputs

Power Input

troublEshooting

Problem

Solution

No reading at controller

· Check that + and - polarity is observed in 

the wiring.

calibration

Before beginning calibration, establish normal load conditions.

A.  To monitor under-current (belt loss, coupling shear, status):

"

OK!

!

OK!

"

OK!

1. Turn setpoint screw counterclockwise 
until Status LED turns on.

2. Slowly turn the screw clockwise to find 
the point at which the Status LED just turns 
off.

Turn the screw an additional 1/4 turn 
counter-clockwise from the position 
determined in step 2 above. The Status LED 
should be ON. The sensor is now calibrated to 
indicate amperage flow below normal levels. 

B.  To monitor over-current (mechanical problems, seized impeller):

"

OK!

!

OK!

45"564

OK!

45"564

4FUQPJOU

4FUQPJOU

Setpoint Status

Setpoint

Status

STOP

The sensor threshold is now balanced at the amperage level being 
monitored. Proceed to A or B below.

Turn the screw an additional 1/4 turn clockwise 
from the position determined in step 2 above. If 
the current exceeds this trip point, the contact 
will close.

H5800 sensor

H5800 sensor