background image

Z203521-0B 

PAGE 2 

©2012 Veris Industries   USA 800.354.8556 or +1.503.598.4564  / [email protected]  

03121

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of  Veris Industries, L.L.C. in the USA and/or other countries.

TM

V100DC

INSTALLATION GUIDE

N.C.

Common

10-30VDC

LOW

wht/blue

COMM

wht/yellow

Common

N.O.

CONTACT OUTPUT

CONTROL SYSTEM INPUT

White

YELLOW

White

ORANGE

blue

 

blue

 

yello

yello

WIRING EXAMPLE

Nipple mount directly to a panel

Nipple mount to any 2x or 4x electrical box

To Load

To Controls

COIL

CONT

ACTS

To Load

To Controls

Wire 
Nut

CO

IL 

CONTACTS

WIRING COLOR CODES

CONTACT AND COIL SPECIFICATIONS

Pull in Voltage 

  DC

10-30V.....................................     9

Drop Out Voltage 

  DC

10-30V.....................................   3

Voltage 

Coil Current

 DC

10V.......................................... 14mA

12V.......................................... 14mA

24V.......................................... 16mA

30V.......................................... 18mA

TYPICAL COIL PERFORMANCE

CONTACT RATINGS

Resistive

..............  10A@277VAC, 28VDC

Motor

.................... 120VAC, 1/3HP N.O. & 1/6HP N.C.

 

240VAC, 1/3HP N.O. & 1/6HP N.C.

 

277VAC, 1/4HP N.O. & 1/8HP N.C.

Pilot Duty

............. 277VAC, (1.7A), 480VA N.O.

Ballast

..................  277VAC, 1.7A

Tungsten

............... 120VAC, TV3 N.O. TV2 N.C.

Gold Flash

............. Yes

Reviews: