Z203521-0B
PAGE 2
©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
03121
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
TM
V100DC
INSTALLATION GUIDE
N.C.
Common
10-30VDC
LOW
wht/blue
COMM
wht/yellow
Common
N.O.
CONTACT OUTPUT
CONTROL SYSTEM INPUT
White
YELLOW
White
ORANGE
blue
blue
yello
w
yello
w
WIRING EXAMPLE
Nipple mount directly to a panel
Nipple mount to any 2x or 4x electrical box
To Load
To Controls
COIL
CONT
ACTS
To Load
To Controls
Wire
Nut
CO
IL
CONTACTS
WIRING COLOR CODES
CONTACT AND COIL SPECIFICATIONS
Pull in Voltage
DC
10-30V..................................... 9
Drop Out Voltage
DC
10-30V..................................... 3
Voltage
Coil Current
DC
10V.......................................... 14mA
12V.......................................... 14mA
24V.......................................... 16mA
30V.......................................... 18mA
TYPICAL COIL PERFORMANCE
CONTACT RATINGS
Resistive
.............. 10A@277VAC, 28VDC
Motor
.................... 120VAC, 1/3HP N.O. & 1/6HP N.C.
240VAC, 1/3HP N.O. & 1/6HP N.C.
277VAC, 1/4HP N.O. & 1/8HP N.C.
Pilot Duty
............. 277VAC, (1.7A), 480VA N.O.
Ballast
.................. 277VAC, 1.7A
Tungsten
............... 120VAC, TV3 N.O. TV2 N.C.
Gold Flash
............. Yes