3.0 3508 Controller
ALM (Alarm) indicator. The alarm may also switch an output – usually a relay to allow
external devices to operate when an alarm occurs. Alarms only operate if they have
been configured and are dependent on customer requirements.
How to acknowledge an alarm will depend on the type of latching which has been
configured. A non-latched alarm will reset itself when the alarm condition is removed. A
latched alarm requires acknowledgement with the 'ACK' function before it is reset.
If an alarm has been activated, the red 'ALM' indicator will flash and the text will indicate
the type of alarm.
To acknowledge an alarm and cancel the 'ALM' indicator, press
and
together.
3.8.14
Program Example 1
The following sequence of entries creates and runs the program shown graphically
below.
1. Turn the controller SP down to '0' by pressing down
.
2. Press page
until 'Prog Segments Used' is displayed. On P10 or P25 models press
up
or down
to select a new program number, (a program with only 1 segment).
3. Press scroll
until 'Holdback Value' is displayed. Default ‘0’ degrees.
4. Press scroll
until 'Ramp Units' is displayed. Press up
or down
to set to ‘Min’
5. Press scroll
until 'Cycles' is displayed. Default ‘1’
6. Press scroll
until 'Segment 1' is displayed
7. Press scroll
until 'Segment Type' is displayed. Press up
or down
to select
'Rate"
8. Press scroll
until 'Holdback Type' is displayed. Default ‘Off’
9. Press scroll
until 'Target SP' is displayed. Press up
or down
to set to ‘400’
degrees.
10. Press scroll
until 'Ramp Rate' is displayed. Press up
or down
to set to ‘5.0’
degrees per minute.
Repeat steps 6 to 10 for 4 more segments. Set 'Holdback' to the default ‘Off’. Enter the
following parameters and values:
Segment Type Dwell Duration ‘30:00.0’ minutes
Segment Type Step Target SP ‘600’ degrees
Segment Type Dwell Duration ‘30:00.0’ minutes
Segment Type Time Target SP ‘200’ degrees, Duration ‘2:00:0’ hours
Finish the program with an 'End' segment:
11. Press scroll
until 'Segment Type' is displayed. Press up
or down
to select
'End'
24
Summary of Contents for CARBOLITE GERO HTF 17/10
Page 7: ...Caution Double Pole Neutral Fusing 7 1 0 Symbols and Warnings ...
Page 38: ...4 0 3508 Dual Loop Cascade Power Limit View 38 ...
Page 60: ...8 0 Repairs and Replacements 60 ...
Page 65: ...G Grey GR Y Green Yellow 65 10 0 Wiring Diagrams ...
Page 69: ...Notes Service Record Engineer Name Date Record of Work ...