24
25
NIGHT OCCUPANCY THRESHOLD
00-60
(01*) Select the minimum period of time (in minutes) for which
occupancy needs to be detected in order to consider the room
occupied during the “Night Occupancy”period.
When occupancy is detected while room is considered
unoccupied during the “Night Occupancy” period, the
thermostat will instantaneously switch to occupied mode for a
duration of “Night Occupancy Threshold” selected here.
If occupancy is detected for a period of time shorter than the
“Night Occupancy Threshold” selected here, the thermostat
will automatically revert to unoccupied mode and continue to
observe energy saving functions that were in effect before the
room became occupied.
If occupancy is detected for a period of time longer than the
“Night Occupancy Threshold” selected here, the thermostat will
disable the occupancy sensor and consider the room occupied
until the end of the “Night Occupancy” period.
This feature ensures that energy saving functions that may
affect guest comfort will not come in effect during the “Night
Occupancy” period.
Thermostat Settings
FORCED 2ND STAGE HEATING
00-60
(30*) Select a number of minutes 1st STAGE heating will run
before 2nd STAGE heating is automatically initiated if the
temperature setpoint is not reached and the 2nd STAGE
heating is not initiated through differential settings.
This feature allows automatically turning on 2nd STAGE
heating to avoid excessive compressor use.
Set to
00
to disable the feature.
Thermostat Settings