Verasys Boiler Controller Quick Start Guide

2

Wiring the controller

The system bus terminal block is a blue, removable, 4-terminal plug 
that fits into a board-mounted jack. To wire the controller, complete 
the following steps:

1.

Wire the removable system bus terminal block as shown in 
Figure .

2.

Wire any other devices that you want to connect on the system 
bus in a daisy-chain configuration using 3-wire twisted, shielded 
cable as shown in Figure 5.

Figure 4: 

System bus terminal block wiring

Figure 5: 

Daisy-chain wiring configuration

Enable the end of line (EOL) switch

If the controller is at the beginning or end of the line on the system 
communication bus, you must activate the EOL switch.
1. To disengage and remove the plastic cover press down on the top 

of the controller.

Note: 

Ensure that you do not disconnect the ribbon cable that 

connects the controller to the board display.

Note: 

The EOL switch is a red block with a white switch located 

directly above the system bus terminal block. 
2. Turn the EOL switch on by moving the white switch to the right. 

Wiring the supply power terminal block

The 24 VAC supply power terminal block is a gray,  removable, 3-
terminal plug that fits into a board-mounted jack on the top right of the 
controller. 
Wire the 24 VAC supply power wires from the transformer  to the HOT 
and COM terminals on the terminal plug, as shown in Figure 6

Note: 

Do not use the middle terminal on the supply  power 

terminal block.

Note:

The supply power wire colors may be different on 

transformers from other manufacturers. Refer to the transformer 
manufacturer’s instructions and the project installation drawings for 
wiring details.

Figure 6: 

Supply power terminal block wiring

Wiring options

 

Configurable outputs 1, 2, and 3, and triac binary outputs 8 and 9 are 
rated for a maximum current draw of 0.5 A. It is best practice to use 
pilot relays when you use these outputs to drive contactors.
You can choose a pilot relay with a manual override function. You can 
also use software to reverse the polarity of the output. This means 
that you can drive contactors with contacts that are normally open 
(fail off) or normally closed (fail on). 

Table 1:

Daisy-chain wiring configuration

No.

Description

1

Terminating device on the system bus

2

System bus terminal block plugs

3

Daisy chained device on a system bus segment

4

To next device on the system bus segment

CO

M

SHD

1

2

3

4

4

CO

M

SHD

CO

M

SHD

Table 2:

Supply power terminal block wiring

No.

Description

1

Supply power terminal block jack

2

Supply power terminal block plug

3

Wires from Johnson Controls® 90 VAC to 24 VAC, Class 2 
power transformer

(COM)

(24 VAC)

HOT

COM

24V~

HOT

COM

1

2

3

Summary of Contents for LC-VAC3000-0

Page 1: ...or more information or to access Quicklit scan the following QR codes Mounting the controller To mount the controller complete the following steps 1 Mount a 20 cm 8 in section of 35 mm 1 3in DIN rail...

Page 2: ...ight of the controller Wire the 24 VAC supply power wires from the transformer to the HOT and COM terminals on the terminal plug as shown in Figure 6 Note Do not use the middle terminal on the supply...

Page 3: ...PUT COM VAC3000 OUT1 OCOM1 OUT2 OCOM2 OUT3 OCOM3 24V COM 24 VAC OUT IN 18 ICOM 18 15V COM MOD BUS COM OCOM4 OUT4 PWM COM OUT5 PWM PWM OUT6NO OCOM6 OUT7NO OCOM7 OUT8NO OCOM8 OUT9NO OCOM9 OUT11 A OUT11...

Page 4: ...s BLR4 A 29 Boiler pump 1 status BP1 S 30 Boiler pump 2 status BP2 S 31 Boiler pump 3 status BP3 S 32 Boiler pump 4 status BP4 S 33 Secondary hot water pump 1 status SHWP1 S 34 Secondary hot water pum...

Page 5: ...y contact 3 Boiler 3 isolation valve command BLR3 ISO C Relay contact 4 Boiler 4 isolation valve command BLR4 ISO C Relay contact 5 Secondary hot water pump 1 command SHWP1 C RIBU1C 6 Secondary hot wa...

Page 6: ...umps Sets the number of primary pumps Adjustable 1 4 Primary Pump Operation Type Sets the pumps operation type Adjustable Duty Standby Lead Lag Number of Secondary Pumps Sets the number of secondary p...

Page 7: ...trols declares that this product is also in compliance with the essential requirements and other relevant provisions of the EMC Directive Declared as Electronic Independently mounted control suitable...

Reviews: