Verasys Boiler Controller Quick Start Guide

 Refer to th

QuickLIT website

 for the most up-to-date version of this document.

1

Verasys Boiler Controller

Quick Start Guide

LC-VAC3000-0

Code No. Lit 12013353

 

Issued June 2019

Figure 1:  LC-VAC3000-0

About this guide

This quick start guide provides the basic information you need to 
configure and install the Boiler Controller and application. 

For further information, refer to the 

Verasys® 32 Point 24 VAC 

Application Controller Installation Instructions (24-10143-01515)

, and

 

Verasys Boiler Controller Application Not

e (LIT-12013275) on 

QuickLit. 

For more information or to access Quicklit, scan the following QR 
codes:

Mounting the controller

To mount the controller, complete the following steps:

1.

Mount a 20 cm (8 in.) section of 35 mm (1.3 in.) DIN rail 
horizontally. 

Note: 

Mount the controller in the horizontal position.

2.

On the back of the controller, extend the two mounting clips as
shown in the following figure.

3.

Place the controller on the DIN rail.

4.

To secure the controller on the DIN rail, push the bottom
mounting clips up as shown in the following figure.

5.

To remove the controller from the DIN rail, pull the  bottom
mounting clips out to the extended position and carefully lift the
controller off the DIN rail

LC-VAC3000-0 QR code

QuickLit QR code

Figure 2: 

Pull lower mounting clips down 

Figure 3: 

Pull lower mounting clips down 

Summary of Contents for LC-VAC3000-0

Page 1: ...or more information or to access Quicklit scan the following QR codes Mounting the controller To mount the controller complete the following steps 1 Mount a 20 cm 8 in section of 35 mm 1 3in DIN rail...

Page 2: ...ight of the controller Wire the 24 VAC supply power wires from the transformer to the HOT and COM terminals on the terminal plug as shown in Figure 6 Note Do not use the middle terminal on the supply...

Page 3: ...PUT COM VAC3000 OUT1 OCOM1 OUT2 OCOM2 OUT3 OCOM3 24V COM 24 VAC OUT IN 18 ICOM 18 15V COM MOD BUS COM OCOM4 OUT4 PWM COM OUT5 PWM PWM OUT6NO OCOM6 OUT7NO OCOM7 OUT8NO OCOM8 OUT9NO OCOM9 OUT11 A OUT11...

Page 4: ...s BLR4 A 29 Boiler pump 1 status BP1 S 30 Boiler pump 2 status BP2 S 31 Boiler pump 3 status BP3 S 32 Boiler pump 4 status BP4 S 33 Secondary hot water pump 1 status SHWP1 S 34 Secondary hot water pum...

Page 5: ...y contact 3 Boiler 3 isolation valve command BLR3 ISO C Relay contact 4 Boiler 4 isolation valve command BLR4 ISO C Relay contact 5 Secondary hot water pump 1 command SHWP1 C RIBU1C 6 Secondary hot wa...

Page 6: ...umps Sets the number of primary pumps Adjustable 1 4 Primary Pump Operation Type Sets the pumps operation type Adjustable Duty Standby Lead Lag Number of Secondary Pumps Sets the number of secondary p...

Page 7: ...trols declares that this product is also in compliance with the essential requirements and other relevant provisions of the EMC Directive Declared as Electronic Independently mounted control suitable...