Verasys® 32 Point 24 VAC Application Controller Installation Instructions
25
Setup and Adjustments
Setting the Device Addresses
Use the local display or MAP Gateway to set up device addresses. Verasys field controllers are devices on MS/TP
Sensor buses. Before operating field controllers on a bus, you must
set a valid and unique device address for each
controller on the bus through the local display or MAP gateway. Device addresses 4 through 127 are the valid
addresses for these controllers.
Refer to the Verasys® BACnet® MS/TP Communications Bus Technical Bulletin (LIT-12012362) for more
information on field controller device addresses and how to set them on MS/TP buses.
Troubleshooting
Follow the Status LEDs on the front of the controller and see Table 9 to troubleshoot the controller
.
Table 8: SA Bus Device Address Description
Device Address
Use on Description
0
Reserved for System Bus Supervisory Controller. Not for use on field controllers.
1 to 3
Reserved for peripheral devices. Not for use on field controllers.
117
Reserved for SBH.
4 to 127
Used for MS/TP devices. also known as field controllers, that are hardwired to a Sensor and System bus.
Table 9: Status LEDs and Descriptions of LED States
LED Label
LED Color
Normal LED
State
Description of LED States
POWER
Green
On Steady
Off Steady = No Supply Power. Check the Output wiring for
short circuits and cycle power to the controller.
On Steady = Power Connected
FAULT
Red
Off Steady
Off Steady = No Faults
On Steady = Device Fault: no application loaded; Main Code
download required if controller is in Boot mode.
Blink - 2 Hz = Download or Startup in progress, not ready for
normal operation.
Sensor BUS
Green
Blink - 2 Hz
Blink - 2 Hz = Data Transmission (normal communication).
Off Steady = No Data Transmission (Auto baud in progress).
On Steady = Communication lost, waiting to join.
System BUS
Green
Blink - 2 Hz
Blink - 2 Hz = Data Transmission (normal communication).
Off Steady = No Data Transmission (Auto baud in progress).
On Steady = Communication lost, waiting to join.
MODBUS
Green
Blink - 2 Hz
Blink - 2 Hz = Data Transmission (normal communication).
Off Steady = No Data Transmission (Auto baud in progress).
On Steady = Communication lost, waiting to join.