Setting up setpoints
Page 4/4
The setpoints for schedule entries are programmed on page 4/4.
Setting up setpoints.
Press the
button to select a parameter.
Then use the
and
buttons to set the desired parameter value.
You may program up to three entries. Set the fan speed and temperature for each setpoint.
UNIT PARAMETER SETUP
To set up the unit parameters enter the user parameters menu and
select «Parameters».
The «Parameters» menu consists of four pages. To navigate between
the pages use the
and
buttons.
Page 1/04. Setting up fan speed.
Use the
button to select the supply or exhaust fan speed as
necessary and then press the
and
buttons to set the speed
value as a percentage of the maximum speed.
After that press the
button to save the settings.
The «
Main sensor»
parameter allows changing the temperature
measuring location to account for the value and subsequent
processing by the firmware.
If the unit serves a number of spaces the parameter value should be
set to:
«Exh. air»
If the parameter value is selected
«in th-Tune»
, the control panel
must be installed in the space supplied by the unit.
Page 2/04. Setting up temperature setpoints.
Press the
button to select the temperature setpoint and then use
the
and
buttons to define the setpoint value.
After that press the
button to save the settings.
Т1
is the setpoint for the supply air temperature at which the unit
will switch to a lower speed in case of failure to attain the pre-
programmed temperature conditions.
Т4
is the temperature increase relative to
T1
for switching to the
pre-programmed speed.
Page 3/04. Setting up humidity/СО2 sensor feedback operation.
The
«Humidity sensor»
parameter enables changing the humidity
measurement location. To control the humidity level at the control
panel mounting location (if the panel is equipped with a humidity
sensor) select the
«th-Tune»
parameter.
If the unit is equipped with an external humidity/CO
2
sensor
and the
«exhaust air»
parameter is selected, the humidity/CO
2
measurements are taken at the sensor mounting location.
The fan speed (if the Auto fan mode is selected) will vary within the
parameters defined by setpoints from U1 and U3 to U2 and U4 so
that the humidity/CO
2
levels are maintained below the
«Humidity/
СО
2
set.»
threshold value.