17
www.ventilation-system.com
pGD1
Connect the pGD1 control panel to the controller
connector (see figure on page 13) using the 6P6C (PLUG-
6P6C-P-C2) phone plug. The maximum length of the phone
cable is 50 m.
The pGD1 offers extended functionality and has identical
settings entered via the controller screen (see «Controller
functions and menu»).
The main page of the control panel menu displays the following information:
• date and current time
• indoor temperature (the temperature registered by each sensor can be browsed by pressing the «Up» and «Down» buttons: outdoor tem-
perature, the temperature downstream of the heat exchanger, at the condenser unit and in the exhaust air duct)
• unit operation mode
• temperature setpoint
• selected speed
• scheduled operation on/off
The main page enables access to the user or engineering menu containing extended information specific to the unit operation and detailed
parameters for adjustment.
PLAN NETWORK CONFIGURATION WHILE USING AN EXTERNAL CONTROL PANEL (pGD1).
To enable interaction with the control panel boot up the controller in the pLan mode and assign the following pLan addresses to the controller
and the control panel:
Controller
— 1;
Control panel (pGD1) — 30, 31 or 32 (factory default value).
SETTING PLAN ADDRESS FOR THE CONTROL PANEL (pGD1).
1. Connect the control panel to the controller and power up the controller.
2. Ignore any information which might show on the display screen and simultaneously press the «Up», «Down» and «Enter» buttons and hold
them for 3-5 seconds. After this time the message «Display address setting…..32» appears on the display screen.
3. Move the cursor to the address setting field using the «Enter» button. Use the «Up» and «Down» buttons to set the desired address value
and press «Enter».
SETTING CONTROLLER PLAN ADDRESS VIA THE BUILT-IN CONTROL PANEL.
1. Power off the controller.
2. Power up the controller and immediately press the «Up» and «Alarm» buttons simultaneously. Hold the buttons pressed until the controller
page appears on the screen (wait for about 15 seconds):
3. Use the «Up» and «Down» buttons to set the device address to 1.
4. Press the «Enter» button within 10 seconds to confirm. Failure to press the button within 10 seconds will cause the controller to close the
address setting page automatically while keeping the original address value.
5. Upon confirmation the controller will restart with a new pLan address automatically.
SETTING CONTROLLER PLAN ADDRESS VIA pGD1 CONTROL PANEL.
To set the controller address use the pGD1 panel to set the control panel (dGD1) address to 0. To do this follow the steps described in
«SETTING
PLAN ADDRESS FOR THE CONTROL PANEL (pGD1)»
paragraph above. Upon setting the control panel address to zero by using the respective
buttons on the external control panel follow the steps described in
«SETTING CONTROLLER PLAN ADDRESS VIA THE BUILT-IN CONTROL
PANEL»
paragraph.
After setting the controller address set the pLan address of the control panel (pGD1) to 30, 31 or 32.