1. AC208EM2 (24VAC) control panel (digital thermostat).

The AAC208EM2 (24VAC) control panel (digital thermostat) provides:
•  Switching the air handling unit ON/OFF.
•  Selecting one of 3 speed modes.
•  Display of room temperature.
• Scheduled 

operation.

2. P3-1-300 speed switch.

The P3-1-300 rotary speed switch is used for switching one of three speeds and for switching 
the unit on/off .

3. CO

2

 sensor.

The CO

2

 sensor with a no-contact is used in utility and public spaces and ensures high-speed 

ventilation when the level of carbon dioxide is higher than the set maximum value.

Any CO

2

 sensor commutating voltage of 24 V (0.1 A) can be used for connection to the unit.

WARNING: The CO

2

 sensor must close a contact if the CO

2

 level exceeds the set point and 

open it when the CO

2

 level falls below the set point.

4. Mechanical humidity sensor.

The mechanical humidity sensor with a no-contact is used for humidity level control in the room. If humidity exceeds the set point, the unit 
switches from the regular operation mode to the high speed mode. The unit will operate in the high-speed ventilation mode until the relative 
humidity falls below the set point. Adjust the level of humidity if necessary. 

Any mechanical humidity sensor that can commutate 24 V (0,1 A)voltage is suitable for connection to the unit. 

WARNING: The humidity sensor must close a contact if the humidity level exceeds the set point and open it when the humidity level 
falls below the set point.

5. Mechanical timer

The remote mechanical timer must be installed in areas of air pollution. The timer is used for switching from regular operation mode to the high 
speed ventilation mode. Up to 5 timers can be installed in a building within a distance to the unit of maximum 150 m. 

Any mechanical timer commutating voltage of 24 V (0.1 A) can be used for connection to the unit. 

6. ON/OFF switch.

The ON/OFF switch must be installed in areas of air pollution. When the contacts of the ON/OFF switch are closed the unit switches to a high 
speed ventilation mode. Open the contacts of the ON/OFF switch to return to a continuous low-speed ventilation mode.

Any switch commutating voltage of 24 V (0.1 A) can be used for connection to the unit. 

Summary of Contents for VUE2 200 P

Page 1: ...USER S MANUAL VUT2200P VUE2200P VUTE2200P Heat energy heat and energy recovery air handling unit...

Page 2: ...Unitdesignandoperatinglogic 7 Installationandset up 8 Connectiontopowermains 11 Unitcontrol 12 Technicalmaintenance 14 Troubleshooting 15 Storageandtransportationregulations 15 Manufacturer swarranty...

Page 3: ...e VU_2 200 P heat energy heat and energy recovery air handling unit hereinafter referred to as the unit UNIT MOUNTING AND OPERATION SAFETY PRECAUTIONS Disconnect the unit from power mains prior to any...

Page 4: ...the unit generates unusual sounds odour or emits smoke disconnect it from power supply and contact the Seller Do not open the unit during operation Do not direct the air flow produced by the unit towa...

Page 5: ...osive mixtures evaporation of chemicals sticky substances fibrous materials coarse dust soot and oil particles or environments favourable for the formation of hazardous substances toxic substances dus...

Page 6: ...ERALL DIMENSIONS OF THE UNIT MM UNIT TECHNICAL DATA Ventilation mode speed LOW low MED medium MAX maximum Unit supply voltage 50 Hz V 1 230 Maximum fan power W 67 104 142 Fan current A 0 58 0 63 0 68...

Page 7: ...erties of the heat exchanger material the unit drainage is not required Heat recovery minimizes heat losses which reduces the cost of space heating in the cold season Freeze protection The heat exchan...

Page 8: ...ake side equal to 3 air duct diameters on outlet side If the air ducts are too short or not connected protect the unit parts from ingress of foreign objects e g by covering the spigots with a pro tect...

Page 9: ...ust have an opening or a hook to fix the three sided thumbscrews to the unit Remove all the three sided thumbscrews from the unit for suspended mounting by means of belts Then insert them into a mount...

Page 10: ...e at least 3 Before starting the unit fill the system with water and check that the U trap is always filled with water Check for any obstructions to the free flow of water into the sewage system to pr...

Page 11: ...and check the installation The wiring diagram of the unit is shown in the figure below The TS1 thermostat relay in the unit casing provides freeze protection of the heat exchanger during cold season...

Page 12: ...tivation of any connected controls the unit switches to high speed ventilation mode Thermostat Medium speed Low speed Standby mode Two wire control panel NO Thermostat Two wire control panel NO Medium...

Page 13: ...ration mode to the high speed mode The unit will operate in the high speed ventilation mode until the relative humidity falls below the set point Adjust the level of humidity if necessary Any mechanic...

Page 14: ...me dust may accumulate inside the fans and reduce the fan performance and supply air flow Clean the fans with a soft brush or cloth Do not use water aggressive solvents or sharp objects as they may da...

Page 15: ...a dry closed ventilated premise with temperature range from 5 C to 40 C Vapoursorparticleswhichcancausecorrosionordamagetheinsulationorconnectiontightnessarenotallowedinthestorageenvironment Use hois...

Page 16: ...the Seller for warranty service The manufacturer s warranty does not apply to the following cases User s failure to submit the unit with the entire delivery package as stated in the user s manual inc...