background image

10

VUT/VUE HB(E) ЕС

www.ventilation-system.com

CONDENSATE DRAINAGE

All the VUT and VUE units are equipped with a drain pan.
The drain pan in energy recovery units (VUE) is not used, since condensate is not formed due to the transfer of moisture from one air 
stream to the other through the enthalpy membrane. 
Temperature differences between supply and extract air flows in heat recovery units (VUT) lead to condensate formation. Condensate is 
formed in the heat exchanger, then it is collected in the drain pan and removed outside by the drain pipes. Connect the part of the drain 
hose at the outside of the unit to the sewage system. 

min 3°

Drain hose

U-trap

Sewage system

Drain pipe

CAUTION! 

To ensure the flow of water, pipes must be mounted with a slope of at least 3°.
Provide free drainage for the condensed water, otherwise it is accumulated inside the unit that may cause the equipment damage and 
condensate outflow to the room.
The condensate drainage system is designed for normal operation in premises with air temperatures above 0 °C!
If the expected ambient air temperatures are below 0 °C, the condensate drainage system must be equipped with heat insulation and 
pre-heating facilities. 

Summary of Contents for VUE 300 HB EC

Page 1: ...VUT 300 HB E EC VUT 400 HB E EC VUT 700 HB E EC VUE 300 HB E EC VUE 400 HB E EC VUE 700 HB E EC Heat recovery air handling unit USER S MANUAL ...

Page 2: ...ules and safety precautions noted in this user s manual may result in an injury or unit damage After a careful reading of the manual keep it for the entire service life of the unit While transferring the unit control the user s manual must be turned over to the receiving operator This user s manual is a main operating document intended for technical maintenance and operating staff The manual conta...

Page 3: ...e electric parts of the unit against ingress of water Do not allow children to operate the unit Disconnect the unit from power mains prior to any technical maintenance Do not store any explosive or highly flammable substances in close proximity to the unit When the unit generates unusual sounds odour or emits smoke disconnect it from power supply and contact the Seller Do not open the unit during ...

Page 4: ...other spaces with high humidity Due to the ability to save heating energy by means of energy recovery the unit is an important element of energy efficient premises The unit is a component part and is not designed for stand alone operation It is rated for continuous operation Transported air must not contain any flammable or explosive mixtures evaporation of chemicals sticky substances fibrous mate...

Page 5: ...30 Maximum unit power W 182 182 289 289 336 336 Maximum unit current without an electric heater A 1 4 1 4 2 1 2 1 2 4 2 4 Electric heater power W 2800 2800 2800 2800 3600 3600 Electric heater current A 12 2 12 2 12 2 12 2 15 6 15 6 Maximum unit power with an electric heater W 182 2982 182 2982 289 3089 289 3089 336 3936 336 3936 Maximum unit current with an electric heater A 1 4 13 6 1 4 13 6 2 1 ...

Page 6: ...er replacement are located on the service side of the unit Service side change is available The VUT VUE HBE A21 models are equipped with a built in reheater for heating the supply air to a more comfortable temperature An NKD electric duct heater can be optionally connected to the VUT VUE HB A21 units The heaters operate automatically according to the temperature sensor readings The NKD heater must...

Page 7: ...or monitoring supply filter clogging 9 Differential pressure switch for monitoring extract filter clogging 10 Filter maintenance access hole 11 Inspection hatch for access to the control unit 12 Condensate drip tray 13 Condensate drain pan 14 Drain pipe 15 Supply air reheater 16 Wi Fi antenna 17 Set Up Mode on off button 18 Brackets for suspended mounting 19 USB connector service 20 Connector for ...

Page 8: ...unit Undo the screws securing the panels and remove them Remove the heat exchanger with a condensate drip tray Install the panel which is not a service side on the opposite side Move the block with the bypass damper against the stop with the panel and install the heat exchanger with the condensate drip tray to the unit Fix the front panel service side using screws Close the screw caps with the plu...

Page 9: ...the mounting surface as well as the weigh of the unit refer to the Technical data section Fasteners for unit installation should be selected by a qualified technician CAUTION To get the best performance of the unit and to minimize turbulence induced air pressure losses connect the straight air duct sectiontothespigotsonbothsidesoftheunitwhileinstalling Minimumstraightairductlength equalto1airductd...

Page 10: ...the drain pan and removed outside by the drain pipes Connect the part of the drain hose at the outside of the unit to the sewage system min 3 Drain hose U trap Sewage system Drain pipe CAUTION To ensure the flow of water pipes must be mounted with a slope of at least 3 Provide free drainage for the condensed water otherwise it is accumulated inside the unit that may cause the equipment damage and ...

Page 11: ...onductor temperature depending on the wire type insulation length and installation method The external power input must be equipped with an automatic circuit breaker built into the stationary wiring to open the electric circuit in case of overload or short circuit The circuit breaker installation place must provide quick access for emergency shutdown of the unit The trip current of the automatic c...

Page 12: ... with an A21 controller Boost Kamin X1 X3 QF XP CCU PK1 1 2 24V B A GND P1 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 C NO C NO C NO 24V B A GND C NO C NO C NC PE N L1 PE N L 230 VAC L N PE SM1 2 1 SM2 2 1 U U Designation Unit name Cable type Maximum cable length Note CCU Compressor condenser unit 2x0 75 mm2 20 m 3 A 30 DC 250 AC SМ1 Supply air damper actuator 2x0 75 mm2 20 m 3 A 30 DC 250 AC SМ2 Extr...

Page 13: ...e hand screws on the detachable plates and remove them 2 Pull the dirty filters to remove 3 Clean the filters with a vacuum cleaner 4 Put the filters in place and assemble the unit in the reverse order The unit is controlled With a wired wall control panel in units with an A14 controller included in the delivery set With a mobile application and or a wired and wireless wall panel purchased separat...

Page 14: ... cleaner using a slotted nozzle 5 Put the heat exchanger in place and assemble the unit in the reverse order 3 Fan maintenance once per year Even in case of regular maintenance of the filters some dust may accumulate inside the fans and reduce the fan performance and supply air flow Clean the fans with a soft cloth brush or using compressed air Do not use water aggressive solvents or sharp objects...

Page 15: ...impeller blades are soiled Turn the unit off Troubleshoot the motor jam and the impeller clogging Clean the blades Restart the unit Automatic circuit breaker trips following the unit turning on High current consumption caused by a short circuit Turn the unit off Contact the Seller Low air flow Low set fan speed Set higher speed The filters and the fans are clogged the heat exchanger is clogged Cle...

Page 16: ...e unit the user s manual with the purchase date stamp and the payment paperwork certifying the purchase The unit model must comply with the one stated in the user s manual Contact the Seller for warranty service The manufacturer s warranty does not apply to the following cases User s failure to submit the unit with the entire delivery package as stated in the user s manual including submission wit...

Page 17: ...th the user s manual The warranty terms are acknowledged and accepted Customer s Signature The VUT VUE _________ HB E ЕС А___ unit has been connected to power mains pursuant to the requirements stated in the present user s manual Installation Stamp Seller Address Phone Number Installation Technician s Full Name Installation Date Signature The unit has been installed in accordance with the provisio...

Page 18: ...18 VUT VUE HB E ЕС www ventilation system com ...

Page 19: ...19 www ventilation system com ...

Page 20: ...V109 1EN 01 ...