CONDENSATE DRAINAGE
The unit is equipped with a drain pipe for condensate drainage (only for the unit VENTS VUT 100
P mini). The connection of the unit to drain system is shown in fig. 5.
Connect the condensate drain pipe (1), U-traps (3) and the drainage system with metal, plastic
or rubber pipes .
The pipes should be sloped down by min. 3 degrees.
Before starting operation of the unit fill the system with water and check that U-trap is always
filled with water. Make sure that the water drainage is correct. Wrong connection to drainage system
may result in unwanted water ingress to the room.
The unit with a condensate drainage system is designed for operation at the ambient tempera-
ture above 00C. If the unit is operated in the environment below 00C it must be thermal-insulated and
equipped with heating.
Check the correct installation of the U-trap considering low pressure in the system produced
by the supply fan (fig.5). In this case the maximum developed pressure is 115 Pa and dimension A is
about 100 mm and dimension B is about 80 mm.
Fig. 5
To gain the best performance of the unit while mounting provide a straight 1 m duct section
in front and behind the unit . If the unit is installed at the air duct inlet or outlet it shall be equipped
with a grille with the mesh width up to 12.5 mm or any other protecting device to prevent free access
to the unit fans.
2
4
1
3
А
В
min 3°