While mounting the unit provide enough space for its servicing and maintenance. Suspend the 

unit to  ceiling by means of the threaded rod fixed inside the threaded dowel, fig. 3.

MOUNTING AND SETTING-UP

1. Supply fan 

2. Extract fan 

3. Plate cross-flow heat exchanger made of aluminium for the model VENTS VUT 100 P mini or 

paper for the model VENTS VUE 100 P mini. 

4. G4 Supply filter 

5. G4 Extract filter 

6. Thermostatic switch 

7. Condensate drain pipe (for the unit VUT 100 P mini only).

Fig. 3

Minimum access distance for the unit

400

1

0

Fig. 4

Washer 

Nut 

Vibration-absorbing 

rubber 

Nut and counter-nut

min 

1

0

Summary of Contents for VUE 100 P mini

Page 1: ...USER S OPERATION MANUAL Air handling unit with heat energy utilization VENTS VUT 100 P mini VENTS VUE 100 P mini ...

Page 2: ...hnical data Basic dimensions Safety requirements Structure and operating diagram Mounting and setting up Condensatedrainage Unit connection to power mains Unit operation and control logic Servicing and maintenance Troubleshooting Storage and transportation rules Manufacturer swarranty Acceptance certificate Connection certificate Warranty card ...

Page 3: ...ises as well as utilization of extract air heat energy to warm up supply purified air The unit is designed for ceiling mounting The unit is rated for continuous operation always connected to power mains Operating medium must not contain any flammable or explosive mixtures evaporation of chemicals coarse dust soot and oil particles sticky substances or fibrous materials or any other harm ful substa...

Page 4: ...rom solid objects and liquids IP 44 for the unit motors protection from objects equal to or larger than 1 0 mm and splashing water IP 22 for the assembled unit connected to the air ducts protection from objects equal to or larger than 12 5 mm and water tilted at 15 The unit series designation key the basic overall and connecting dimensions external view technical data are shown in fig 1 and in tab...

Page 5: ... 30 38 56 Current A 0 18 0 23 0 34 Air capacity m3 h 57 78 106 Rotation speed min 1 1300 1950 2500 Noise level at 3 m dBa 24 32 41 Maximum operating temperature C 25 up to 50 Casing material Aluzink Insulation material Penophole Heat insulation layer mm 15 Filter extract G4 supply G4 Connecting air duct dia mm 4 х 125 Heat utilization efficiency 68 Moisture utilization efficiency 65 Heat exchanger...

Page 6: ...the unit consider the requirements of the present operation manual as well as general requirements of all applicable local and national building and electrical codes and standards Ground the unit before operating Before connecting the unit to power mains make sure that the unit is free of any visible damages or any other foreign objects inside the casing that can damage the impeller blades Connect...

Page 7: ...UP 1 Supply fan 2 Extract fan 3 Plate cross flow heat exchanger made of aluminium for the model VENTS VUT 100 P mini or paper for the model VENTS VUE 100 P mini 4 G4 Supply filter 5 G4 Extract filter 6 Thermostatic switch 7 Condensate drain pipe for the unit VUT 100 P mini only Fig 3 Minimum access distance for the unit 400 10 Fig 4 Washer Nut Vibration absorbing rubber Nut and counter nut min 10 ...

Page 8: ...e room The unit with a condensate drainage system is designed for operation at the ambient tempera ture above 00C If the unit is operated in the environment below 00C it must be thermal insulated and equipped with heating Check the correct installation of the U trap considering low pressure in the system produced by the supply fan fig 5 In this case the maximum developed pressure is 115 Pa and dim...

Page 9: ...through the terminal block in compliance with the wiring diagram and terminal designation on the fig 6 The wiring diagram is also shown inside the terminal box The terminals on the wiring diagram are marked in compliance with the actual marking in the unit Route the wires into the terminal box through an airtight screwed cable gland located at the side wall of the unit to preserve the electric rat...

Page 10: ...es of the heat exchanger materials the unit does not need condensate drainage Due to energy and heat utilization by the heat exchanger minimizes thermal energy losses and saves heating costs during cold season Air flow in the unit in regulated by the two speed switch P3 1 300 further the switch View of the switch as shown in fig 7 The thermostatic switch 6 fig 2 in the unit casing provides frost p...

Page 11: ...tergent solution or vacuum cleaner 3 Fan inspection once per year Even if you maintain the filters and the heat exchanger regularly in accordance with the above procedures some dust and grease can get accumulated inside the fans and reduce the fan performance Clean the fans with a soft brush or a dry cloth Do not use water and abrasive detergent sharp objects or solVENTS for cleaning to prevent th...

Page 12: ... hood and intake grille and clean those if required make sure that the air ducts are not clogged or damaged Noise vibration The impeller s is are clogged Clean the fan impeller s Fan screw tightening is loose Check the screw tightening Water leakage only for the Vents VUT 100 P mini unit The drain pipe is clogged damaged or wrong arranged Clean the drain pipe Check the drain pipe slope U trap and ...

Page 13: ...ny failures in operation of the unit during the warranty period the manufacturer ac cepts any claims from the Customer if the technical certificate with the description of the malfunction is provided Any unauthorized modifications of the electric connection are not allowed and will void the free warranty service Contact the manufacturer or your local seller for both warranty and post warranty serv...

Page 14: ..._______________________ ____________________________________________________________________________________ Sale date ____________________________ Acceptance certificate The air handling unit with heat utilization VENTS VUT VUE 100 P mini ACCEPTANCE CERTIFICATE CONNECTION CERTIFICATE WARRANTY CARD Company name _______________________________________________________________________ Electrical engi...

Page 15: ...15 ...

Page 16: ...V59 1EN 01 ...

Reviews: