ASYNCHRONOUS ELECTRIC MOTOR STARTING METHODS

There are several methods for starting asynchronous squirrel-cage electric motors.
The most common methods are: direct-on-line (DOL), with a soft starter (SS) or with a frequency converter (FC).

Direct-on-line starting

In case of direct-on-line starting (i.e. by connecting the motor to the electric mains with a simple line contactor), the motor starting 
time significantly increases due to high inertia of the impeller, which, in turn, results in high in-rush starting currents in the circuit. These 
currents of long duration may cause voltage slumps (especially if the feed line section falls short of the requirements), which may affect 
load operation.
The in-rush current consumed by an electric motor in case of DOL starting is 5-8 times larger than the rated value (or even 10-14 times 
larger in some rare instances). It should be noted that the torque developed by the motor also significantly exceeds the rated value.
Upon energisation the motor operates as a transformer with a squirrel-cage secondary winding formed by the rotor cage with a very low 
resistance.
The rotor develops high induced current causing a rush of current in the feed line.
The startup torque during starting averages 0.5-1.5 of the rated torque value.

Despite such advantages as simple construction, high startup current, quick start and low cost, direct-on-line systems are suitable only 
in the following cases:
•  the motor power is low compared to the mains power which limits the adverse effect of the rush of current
•  the driven mechanism does not require gradual speed build-up or is equipped with a damping device to smooth out the inrush
•  the high startup torque has no adverse effects on the operation of the driven mechanism

Soft start. SS starting.

A soft starter gradually increases the voltage supplied to the motor – from the initial to the rated value.
This starting system can be used to meet the following goals:
•  limit the motor current
•  regulate the torque

Regulation by limiting the current sets the maximum in-rush current equal to 300-400 % (or  250 % in some rare instances) of the rated 
current and reduces torque characteristics. This type of regulation is especially suited for turbomachinery such as centrifugal pumps and 
fans.
Regulation by variation of torque optimizes the torque during startup and reduces in-rush current in the circuit. These conditions are 
suitable for mechanisms with constant load resistance.
This type of soft starting may differ in the implementation pattern:
•  motor start
•  motor start and stop
•  device bridging at the end of start sequence
•  start and stop of several motors in stage circuits

Soft start. FC starting.

During the starting the FC raises the frequency from 0 Hz to the electrical mains frequency (50 or 60 Hz). As the frequency is increased 
gradually, the motor can be assumed to operate at its rated speed for a given frequency value. Furthermore, on the assumption that the 
motor runs at its rated speed the nominal torque should be immediately available whereas the current will be approximately equal to 
the rated value.
This starting system is used for speed control and regulation and can be used in the following cases:
•  start with high-inertia load
•  start with high load and limited-capacity power supply source
•  optimization of electric power consumption depending on turbomachinery speed
The aforementioned starting system can be used for all types of mechanisms.

Problems associated with DOL starting

The problems caused by DOL starting may be divided into two groups:
1.  An abrupt start causes mechanical shock, jolts in the mechanism, shock removal of free play etc.
2.  A heavy start cannot be completed.

Let us review three variations of a heavy start:

1. The feed line performance is barely sufficient or insufficient to maintain the induced current.

Typical symptoms: 

Upon starting the circuit breakers at the system input are tripped; the lights, certain relays and contactors go off, 

and the supply generator shuts down.

Solution: 

In the best-case scenario an SS device may help reduce the in-rush current to 250 % of the motor rated current. If this is 

insufficient, an FC is necessary.

Summary of Contents for VKPF

Page 1: ...Duct rectangular fan USER S MANUAL VKP VKPI VKPF VKPFI...

Page 2: ...ractical training in the field of ventilation systems and should be able to work in accordance with workplace safety rules as well as construction norms and standards applicable in the territory of th...

Page 3: ...ed Do not expose the device to adverse atmospheric agents rain sun etc Transported air must not contain any dust or other solid impurities sticky substances or fibrous materials Do not use the unit in...

Page 4: ...ed it must be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a safety hazard Ensure that the appliance is switched off from the supply mains before rem...

Page 5: ...PRIATE TRAINING THE UNIT MUST BE INSTALLED AND CONNECTED ONLY BY PROPERLY QUALIFIED PERSONNEL AFTER THE APPROPRIATE BRIEFING THE CHOICE OF UNIT INSTALLATION LOCATION MUST PREVENT UNAUTHORISED ACCESS B...

Page 6: ...X4 IPX4 IPX4 IPX4 IPX4 Electric motor IP rating IP44 IP44 IP44 IP44 IP54 IP54 IP54 IP54 VKP VKPI 4E 600 300 4D 600 300 4E 600 350 Voltage V 1 220 240 3 400 1 220 240 Frequency Hz 50 60 50 60 50 60 Pow...

Page 7: ...0 735 36 38 VKP 4D 600 350 600 620 640 350 370 390 390 735 36 38 Model Dimensions mm Weight kg B B1 B2 H H1 H2 H3 L VKP 4D 1000 500 1000 1020 1040 500 520 540 720 1150 126 0 Model Dimensions mm Weight...

Page 8: ...303 Current A 0 67 3 10 1 70 1 59 0 8 Maximum air flow m3 h 1490 2350 2350 1550 1620 RPM min 1 930 1230 1300 890 910 Sound pressure level at 3 m distance dBA 45 38 57 47 56 47 47 39 51 41 Transported...

Page 9: ...25 40 Ingress protection rating of the unit IPX4 IPX4 IPX4 IPX4 Electric motor IP rating IP54 IP54 IP54 IP54 VKPF VKPFI 6D 700 400 4D 800 500 6D 800 500 8D 800 500 Unit voltage V 50 60 Hz 3 400 3 400...

Page 10: ...300 320 340 375 680 35 VKPF 4D 600 300 600 620 640 300 320 340 375 680 35 VKPF 6E 600 300 600 620 640 300 320 340 375 680 35 VKPF 6D 600 300 600 620 640 300 320 340 375 680 35 VKPF 4E 600 350 600 620...

Page 11: ...0 300 600 620 640 670 300 320 340 480 680 56 VKPFI 4D 600 300 600 620 640 670 300 320 340 480 680 56 VKPFI 6E 600 300 600 620 640 670 300 320 340 480 680 56 VKPFI 6D 600 300 600 620 640 670 300 320 34...

Page 12: ...hat the arrow on the fan casing matches the air flow direction in the system The fan should always be installed on its own hangers so that it does not load the flexible connectors and the connected ai...

Page 13: ...ference only The actual conductor cross section selection must be based on its type the maximum permissible heating insulation length and installation method in the air pipes or inside walls The recom...

Page 14: ...n VKP VKPI 4D 600 300 units with a three phase motor Wiring diagram for VKP VKPI 4D 600 350 units with a three phase motor 400 V 50 60 Hz L N X1 1 2 3 N L QF PE 230 50 60 4 PE L2 L1 QF PE 400 50 60 L2...

Page 15: ...y set The TW1 TW2 TK1 TK2 are the electrical leads of the normally closed contact of the motor overheating protection Connect the contact in series to power circuit of the magnetic starter coil KM1 th...

Page 16: ...or current regulate the torque Regulation by limiting the current sets the maximum in rush current equal to 300 400 or 250 in some rare instances of the rated current and reduces torque characteristic...

Page 17: ...or protection system less sensitive As a result the switching equipment will not be able to detect motor overload in time due to a high current sensing threshold Such problems as mentioned above can o...

Page 18: ...18 VKP VKPI VKPF VKPFI www ventilation system com 1 3 4 5 6 2...

Page 19: ...andling requirements applicable for the particular type of cargo The unit can be carried in the original packaging by any mode of transport provided proper protection against precipitation and mechani...

Page 20: ...ct the Seller for warranty service The manufacturer s warranty does not apply to the following cases User s failure to submit the unit with the entire delivery package as stated in the user s manual i...

Page 21: ...STALLATION CERTIFICATE The VKP _____________ unit is installed pursuant to the requirements stated in the present user s manual Installation Stamp Company name Address Phone Number Installation Techni...

Page 22: ...22 VKP VKPI VKPF VKPFI www ventilation system com...

Page 23: ...23 www ventilation system com VKP VKPI VKPF VKPFI...

Page 24: ...V07EN 04...

Reviews: