![Vents RNS-16 User Manual Download Page 9](http://html1.mh-extra.com/html/vents/rns-16/rns-16_user-manual_1002616009.webp)
9
FUNCTIONAL SWITCHES AND INDICATORS
There are three lights on the indicator panel:
•
Power –
AC mains
(green);
•
Current state –
operation
(yellow) and
alarm/booster heating
(red).
AC mains
Operation Alarm
Current state and malfunction indication
AC mains -
green
Operation -
yellow
Alarm -
red
EVENT
-
-
-
AC mains disconnected
Temperature sensor feedback operation
ON
BLINKING
-
«Temperature boosting:
T set > T flow»
ON
ON
-
«Reaching mode parameters:
T set = T flow»
Power output mode
ON
BLINKING
-
The blinking frequency is proportional to the
power supplied to the heating elements.
Alarms
ON
-
ON
TK50 thermal contact actuation
ON
-
BLINKING
Duct pressure switch signal lost or no enabling
signal
ON
-
BLINKING
double
intermittent
Temperature sensor shorting or sensed value
out of range (t < -40 0C )
ON
-
BLINKING
triple
intermittent
Temperature sensor breakout or sensed value
out of range (t < +90 0C )