Vents KSB 100 K2 User Manual Download Page 5

5

www.ventilation-system.com

TECHNICAL DATA

The unit is rated as a Class I electrical appliance. 

KSB 100 K2

KSB 125 K2

 

KSB 125 K2 S

KSB 150 K2

KSB 160 K2

 

KSB 200 K2

 

KSB 250 K2

  

KSB 315 K2 S

KSB 355 K2

KSB 400 K2

KSB 450 K2 B

KSB 500 К2 (∆)

KSB 500 K2 (

Y

)

Unit voltage [V/50 (60) Hz]

1~ 230 1~ 230 1~ 230 1~ 230 1~ 230 1~ 230 1~ 230 3~ 400 1~ 230 1~ 230 1~ 230 3~230 3~400

Power [W]

58

61

88

84

86

164

320

654

202

349

473

730

780

Current [A] 

0,25

0,28

0,37

0,37

0,38

0,71

1,40

1,10

0,89

2,00

2,35

2,82

1,60

Maximum air flow [m³/h] 

285

330

484

485

500

770

1515

2710

2235

2860

2760

7000

6720

RPM [min-¹]

2530

2560

2670

2620

2670

2580

2615

2600

1330

1380

1350

980

948

Sound pressure level at 3 m distance [dBA]

34

35

40

38

38

42

45

48

48

48

48

56

54

Transported air temperature [°C] 

-25+55 -25+55 -25+55 -25+55 -25+55 -25+55 -25+55 -25+55 -25+55 -25+55 -25+55 -25+55 -25+55

Ingress protection rating 

IPX4

IPX4

IPX4

IPX4

IPX4

IPX4

IPX4

IPX4

IPX4

IPX4

IPX4

IPX4

IPX4

SEC class

C

C

C

C

C

C

-

-

-

-

-

-

-

H

L

B

B1

A1

A2

A

2xØ

D

4xØd

39.8 mm

40 mm

90 mm

Ø 5 mm

2 holes

30 mm

100 mm

2 mm

Overall and connecting dimensions of the fan [mm]

D

H

L

A

A1

A2

B

B1

d

Weight [kg]

KSB 100 K2

99

258

517

414

458

507

420

228

14

13

KSB 125 K2

124

258

517

414

458

507

420

228

13

KSB 125 K2 S

124

280

630

525

568,5

617

533

333

19

KSB 150 K2

149

282

566

493

537

586

470

278

17

KSB 160 K2

159

282

566

493

537

586

470

278

17

KSB 200 K2

198

355

632

535

579

628

535

3575

22.6

KSB 250 K2

248

429

774

666

710

759

677

537

33

KSB 315 K2 S

313

460

857

666

719

747

760

560

9

48

KSB 355 K2

354

500

927

804

857

885

830

641

58

KSB 400 K2

399

578

1024

876

929

957

927

737

78,5

KSB 450 K2 B

449

607

1152

968

1021

1049

1049

858

84

KSB 500 К2 (∆)

KSB 500 K2 (Y)

499

744

1300

1182

1235

1263

1203

993

129

Summary of Contents for KSB 100 K2

Page 1: ...KSB K2 USER S MANUAL Centrifugal duct fan in sound insulated casing...

Page 2: ...observed when installing and operating the unit Disconnect the unit from the power supply prior to any connection servicing maintenance and repair operations Only qualified electricians with a work pe...

Page 3: ...ue to inadvertent resetting of the thermal cut out this unit must not be supplied through an external switching device such as a timer or connected to a circuit that is regularly switched on and off b...

Page 4: ...us substances toxic substances dust pathogenic germs THE UNIT SHOULD NOT BE OPERATED BY CHILDREN OR PERSONS WITH REDUCED PHYSICAL MENTAL OR SENSORY CAPACITIES OR THOSE WITHOUT THE APPROPRIATE TRAINING...

Page 5: ...25 55 25 55 25 55 25 55 25 55 25 55 25 55 25 55 25 55 25 55 25 55 25 55 25 55 Ingress protection rating IPX4 IPX4 IPX4 IPX4 IPX4 IPX4 IPX4 IPX4 IPX4 IPX4 IPX4 IPX4 IPX4 SEC class C C C C C C H L B B1...

Page 6: ...er on the intake side and 3 air duct diameters on the exhaust side No filters or any other similar devices are allowed to be installed in these sections The fan casing is made of aluzinc For easy inst...

Page 7: ...gh of the unit refer to the Technical data section Fasteners for unit mounting should be selected by the service technician 1 Mark the holes for mounting the fan 2 Drill the holes according to the mar...

Page 8: ...nnecting several fans simultaneously provided that their combined capacity and working current remain within the nominal parameters of the regulator External control units are purchased separately sho...

Page 9: ...tion at low temperatures allow the unit to warm up at operating temperature for at least 3 4 hours DISCONNECT THE UNIT FROM POWER SUPPLY BEFORE ANY MAINTENANCE OPERATIONS MAKE SURE THE UNIT IS DISCONN...

Page 10: ...Seller for warranty service The manufacturer s warranty does not apply to the following cases User s failure to submit the unit with the entire delivery package as stated in the user s manual includi...

Page 11: ...TE The unit _____________________________________ is installed pursuant to the requirements stated in the present user s manual Installation Stamp Company name Address Phone Number Installation Techni...

Page 12: ...V143 1EN 02...

Reviews: