5
www.ventilation-system.com
TECHNICAL DATA
The unit is rated as a Class I electrical appliance.
KSB 100 K2
KSB 125 K2
KSB 125 K2 S
KSB 150 K2
KSB 160 K2
KSB 200 K2
KSB 250 K2
KSB 315 K2 S
KSB 355 K2
KSB 400 K2
KSB 450 K2 B
KSB 500 К2 (∆)
KSB 500 K2 (
Y
)
Unit voltage [V/50 (60) Hz]
1~ 230 1~ 230 1~ 230 1~ 230 1~ 230 1~ 230 1~ 230 3~ 400 1~ 230 1~ 230 1~ 230 3~230 3~400
Power [W]
58
61
88
84
86
164
320
654
202
349
473
730
780
Current [A]
0,25
0,28
0,37
0,37
0,38
0,71
1,40
1,10
0,89
2,00
2,35
2,82
1,60
Maximum air flow [m³/h]
285
330
484
485
500
770
1515
2710
2235
2860
2760
7000
6720
RPM [min-¹]
2530
2560
2670
2620
2670
2580
2615
2600
1330
1380
1350
980
948
Sound pressure level at 3 m distance [dBA]
34
35
40
38
38
42
45
48
48
48
48
56
54
Transported air temperature [°C]
-25+55 -25+55 -25+55 -25+55 -25+55 -25+55 -25+55 -25+55 -25+55 -25+55 -25+55 -25+55 -25+55
Ingress protection rating
IPX4
IPX4
IPX4
IPX4
IPX4
IPX4
IPX4
IPX4
IPX4
IPX4
IPX4
IPX4
IPX4
SEC class
C
C
C
C
C
C
-
-
-
-
-
-
-
H
L
B
B1
A1
A2
A
2xØ
D
4xØd
39.8 mm
40 mm
90 mm
Ø 5 mm
2 holes
30 mm
100 mm
2 mm
Overall and connecting dimensions of the fan [mm]
D
H
L
A
A1
A2
B
B1
d
Weight [kg]
KSB 100 K2
99
258
517
414
458
507
420
228
14
13
KSB 125 K2
124
258
517
414
458
507
420
228
13
KSB 125 K2 S
124
280
630
525
568,5
617
533
333
19
KSB 150 K2
149
282
566
493
537
586
470
278
17
KSB 160 K2
159
282
566
493
537
586
470
278
17
KSB 200 K2
198
355
632
535
579
628
535
3575
22.6
KSB 250 K2
248
429
774
666
710
759
677
537
33
KSB 315 K2 S
313
460
857
666
719
747
760
560
9
48
KSB 355 K2
354
500
927
804
857
885
830
641
58
KSB 400 K2
399
578
1024
876
929
957
927
737
78,5
KSB 450 K2 B
449
607
1152
968
1021
1049
1049
858
84
KSB 500 К2 (∆)
KSB 500 K2 (Y)
499
744
1300
1182
1235
1263
1203
993
129