WHILE INSTALLING THE UNIT ENSURE CONVENIENT ACCESS FOR SUBSEQUENT
MAINTENANCE AND REPAIR.
BEFORE MOUNTING MAKE SURE THE CASING DOES NOT CONTAIN ANY FOREIGN
OBJECTS (E.G. FOIL, PAPER).
The fan is suitable both for horizontal and vertical installation. To get the best performance of the unit and to minimize turbulence-
induced air pressure losses, connect the straight air duct section to the spigots on both sides of the unit while installing. Minimum
straight air duct length: equal to 1 air duct diameter on intake side and to 3 air duct diameters on outlet side. No filters or any other similar
devices are allowed to be installed in these sections.
CAUTION!
If necessary, close the fan spigot
with a plug, lubricate the rubber
seal of the spigot with silicone
grease.
Silicone grease for rubber seals
is purchased separately, plugs
are available on request.
!
INSTALLATION AND SET-UP
Model
Dimensions,
in
H1
H2
H1
H2
VKP 100
VKP 125
VKP 125/125x2
2 3/8”
7 7/8”
VKP 150
9 13/16”
VKPF 125/125x2
7 3/4”
Typical installation of fan
2
1
3
Different variants of wall and ceiling mounting of vertical and horizontal fans are shown on Pic. 1-3.
VKP / VKPF
8
vents-us.com