12
4.2.3
C
OOLING PARAMETERS
Name
Default value
Range
Description
PBAND
30.0°C
0 ÷ 999.9°C
Proportional band.
Setting PBAND = 0 means ON / OFF
operation with hysteresis and the entered
HYS parameter.
INT
100 sec
0 ÷ 6000 sec
Integral time
HYS
1.5°C
0.5 ÷ 10.0°C
Hysteresis for two-position control.
If the PBAND = 0, hysteresis determines
the HYS parameter
Operation ON/OFF
CDIS
15
o
C
10 ± 22
o
C
Outside temperature below which the
cooling is turned off (the WINTER mode).
CDIS parameter operation scheme
Outdoor temperature
CDIS
CDIS+1
Cooling disabled
Hysteresis
Enable cooling
Disable cooling
Outdoor temperature
HDIS-1
HDIS
Heating enabled
Hysteresis
Disable heating
Enable heating