Vent-Axia QPTW Series Installation And Wiring Instructions Download Page 4

 

 

 

 

 

 

GENERAL WIRING INSTRUCTIONS 

WARNING – THE FAN AND ANY ANCILLARY CONTROL EQUIPMENT MUST BE 
ISOLATED FROM THE POWER SUPPLY DURING INSTALLATION AND/OR 
MAINTENANCE. THE EQUIPMENT MUST BE EARTHED. 

 

1.

 

All electrical connections should be made by a properly qualified electrician. 

2.

 

All wiring and connections must be carried out in accordance with current 

regulations. 

3.

 

To comply with safety standards, an all pole isolator switch with a contact gap of 

at least 3mm must be fitted adjacent to the fan. 

4.

 

Remove the lid of the QPTW to expose the supply connection terminal blocks 

adjacent to the grommets in the wall of the QPTW. 

5.

 

The thermal protection device fitted is an automatic resetting type which must 

always be included in the circuit. For ducted applications a manual reset is 
required, an ancillary circuit will be required with the TK switch connected into the 
circuit. See page 6 for instructions. 

6.

 

Connect the power supply from the local isolator (via any appropriate controls if 

fitted) to the terminal blocks via the supplied cable gland using between 4.0mm 
and 7.0mm diameter cable. Refer to the wiring diagrams and select the 
appropriate connections for the fan, controller or other devices as being installed. 
If in doubt please ask. 

7.

 

CAUTION

: In order to avoid a hazard due to inadvertent resetting of the thermal 

cut-out, this appliance must not be supplied through an external switching device, 
such as a timer, or connected to a circuit that is regularly switched on and off by 
the utility. 

8.

 

 Ensure that all earth connections have been made. 

9.

 

After making connections to the terminal blocks, replace QPTW lid. Also ensure 

that all cable gland nuts, grommets etc. have been used correctly to prevent the 
ingress of water. 

Fig. 2: Repositioning of shutter assembly. 

Summary of Contents for QPTW Series

Page 1: ...E READ ALL INSTRUCTIONS CAREFULLY BEFORE STARTING INSTALLATION THESE INSTRUCTIONS SHOULD BE LEFT WITH THE END USER Acoustic Fans Twin In line Duct Fan Range QPTW QPTW100C QPTW125C QPTW150C QPTW160C QP...

Page 2: ...ake appropriate action to reduce sound levels A range of products are available for this purpose from Vent Axia This appliance is not intended for use by persons including children with reduced physic...

Page 3: ...and attenuators 5 For horizontal installations parallel fixing brackets are provided for both sides of the unit Fig 1 and extra fixing holes are provided for additional hanger rods 6 All twin units h...

Page 4: ...ired an ancillary circuit will be required with the TK switch connected into the circuit See page 6 for instructions 6 Connect the power supply from the local isolator via any appropriate controls if...

Page 5: ...onent to be incorporated into a ventilation system The final complete system installation that includes the fans MUST meet the requirements of Low voltage Directive 72 23 CEE Machinery Directive 89 39...

Page 6: ...roduct Changeover Panel Changeover Panel with duty share eDemand Changeover Panel QPTW100C 10314200 10314210 QPTW125C 10314200 10314210 QPTW150C 10314200 10314210 QPTW160C 10314200 10314210 QPTW200C 1...

Page 7: ...7 Fig 1 QPTW100C QPTW125C QPTW150C QPTW160C QPTW200C QPTW250C QPTW315C Connected to a changeover panel...

Page 8: ...8 Fig 2 QPTW400C QPTW500C Connected to a changeover panel...

Page 9: ...9 Fig 3 QPTW100C QPTW125C QPTW150C QPTW160C QPTW200C QPTW250C QPTW315C Connected to a changeover panel and auto transformer controller...

Page 10: ...10 Fig 4 QPTW400C QPTW500C Connected to a changeover panel and auto transformer controller...

Page 11: ...11 Fig 5 QPTW400C QPTW500C Connected to a changeover panel and auto transformer controller...

Page 12: ...ex RH10 9YX UK NATIONAL CALL CENTRE Newton Road Crawley West Sussex RH10 9JA SALES ENQUIRIES Tel 0844 8560590 Fax 01293 565169 TECHNICAL SUPPORT Tel 0844 8560593 Fax 01293 539209 For details of the wa...

Reviews: