IMPORTANT:
READ THESE INSTRUCTIONS BEFORE COMMENCING THE INSTALLATION
DO NOT install this product in areas where the following may be present or occur:
•
Excessive oil or a grease laden atmosphere.
•
Corrosive or flammable gases, liquids or vapours.
•
Ambient exhaust air temperatures higher than 40°C or less than –5°C.
•
Relative humidity above 90%
•
Possible obstructions which would hinder the access or removal of the Unit.
•
Sudden ductwork bends or transformations close to the Unit.
SAFETY AND GUIDANCE NOTES
A.
All wiring must be in accordance with the current I.E.E. Regulations, or the appropriate standards of your country.
B.
The Unit should be provided with a local double pole isolator switch having a contact separation of at least 3mm.
The fuse rating should be 3A.
C.
Ensure that the mains supply (Voltage, Frequency and Phase) complies with the rating label.
D.
The Unit should only be used in conjunction with the appropriate Vent-Axia products.
E.
It is recommended that the connection to the terminal box is made with flexible cable/conduit.
F.
The Unit should not be sited within 600mm horizontally of/or 2250mm vertically of a bath/shower tray, in
accordance with the current I.E.E. Regulations for bathrooms.
G.
When the unit is used to remove air from a room containing a fuel-burning appliance, ensure that the air
replacement is adequate for both the fan and the fuel-burning appliance.
H.
The installer must ensure that the Unit intake is located a minimum of 600mm from any flue outlet.
I.
This Unit is designed as an inline ducted unit to be positioned between lengths of ducting. Short duct runs
terminating within 1.5m must incorporate suitable guards unless the unit is mounted higher than 2.3m.
J.
This Unit should not be used where it is liable to be subject to direct water spray from hoses etc.
K.
This Unit handles moisture-laden air, ensure that a condensation drain is fitted.
L.
Certain applications may require the installation of sound attenuation material to achieve the sound levels
required.
M.
Ducted ventilators must be ducted to the outdoors.