TIMER ADJUSTMENT (100SVT AND 100SVH MODELS)
BEFORE ADJUSTING THE TIMER, SWITCH OFF THE MAINS SUPPLY.
TIMER SHOULD ONLY BE ADJUSTED BEFORE OR DURING INSTALLATION.
1.
Remove the fan grille. The overrun timer is factory set to approximately
15 minutes. This timer period can be adjusted between
approximately 3-30 minutes by altering the adjuster on the control PCB.
2.
To REDUCE the operating time, use a small screwdriver to turn the
adjuster Fig.5. CLOCKWISE.
3.
To INCREASE the operating time, use a small screwdriver to turn the adjuster
Fig.5. ANTI-CLOCKWISE.
4.
Replace the fan grille.
HUMIDITY SET-POINT ADJUSTMENT (100SVH MODEL ONLY)
BEFORE ADJUSTING THE CONTROLLER, SWITCH OFF THE
MAINS SUPPLY. HUMIDISTAT SHOULD ONLY BE ADJUSTED BEFORE
OR DURING INSTALLATION.
1.
Remove the fan grille. The controller is factory set to switch on at about
70% RH. The humidity set point can be adjusted from 65-95%RH by
altering the adjuster on the control PCB.
2.
To LOWER the set-point use a small screwdriver to turn the adjuster
Fig.5. ANTI-CLOCKWISE. This makes the controller MORE sensitive.
3.
To RAISE the set-point use a small screwdriver to turn the adjuster
Fig.5. CLOCKWISE. This makes the controller LESS sensitive.
4.
Replace the fan grille.