Vent-Axia Lo-Carbon PureAir Home FD Installation And Wiring Instructions Download Page 6

 

 

400-600mm Joist Dimensions with Unit Clearance Heights 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
E. DIFFUSER GRILLE: 

 
IMPORTANT: PureAir Home FD models are provided with a different diffuser. 
Please note: You cannot fit the heater unit to the diffuser on 

“FD” models.

 

 

The diffuser must be carefully sited to ensure the maximum effectiveness of the system. It should be fitted in the 
ceiling of a common area, ideally above the landing so that the incoming air can reach all the rooms. 
 
Cut the flexible ducting to a suitable length, where possible stretch the ducting to its maximum extent and ensure that 
there is one continuous smooth bend to the diffuser. The ducting 

must

 remain a minimum of 1m in length. 

 
Remove the loft insulation from the location of the diffuser and cut a 240-260mm dia hole in the ceiling.  
 
Ensure the four locking tabs are folded in and then push the spigot in to the hole. Holding the diffuser in place; screw 
the four screws until the locking tabs are holding the diffuser tight against the ceiling (Fig.5).

 It is important not to 

over tighten these screws as this may warp the diffuser.

  

 
Fit the free end of the flexible ducting to the diffuser spigot using the worm drive clip supplied. 
 

The diffuser should not be situated within 1m of a smoke detector, however if this is not possible the Lo-
Carbon PureAir Home has provisions to blank off the airflow for up to two quadrants of the diffuser. Two 
blanking plates are provided; these should be pushed on to the support struts inside the diffuser as 
required. This should be done before the diffuser is installed in the ceiling as when the screws are tightened 
down the plates can no longer be removed. See Fig.6, showing blocking off opposing quadrants, note any 1 
or pair of quadrants can be blocked off as necessary for the install. These block off plates can also be used 
to ensure the supply air is spread across a room rather than directed at close by walls. 
 

Blanking off one side reduces the flow by about 6%, but blanking off two sides reduces the flow by about 20% and so 
if two sides are blanked off then you should consider increasing the fan speed to maintain the appropriate airflow.

 

 
 
 
 
 
 
 
 
 
 
 
 
 

Fig. 5. 

Fig. 6. 

Summary of Contents for Lo-Carbon PureAir Home FD

Page 1: ...H THE ILLUSTRATIONS PLEASE SAVE THESE INSTRUCTIONS Lo Carbon PureAir Home Positive Input Ventilation Unit Stock Ref N 479090 PureAir Home 479091 PureAir Home with Heater 479092 PureAir Home FD Install...

Page 2: ...2...

Page 3: ...ion concerning use of the appliance in a safe way and understand the hazards involved Children shall not play with the appliance Cleaning and user maintenance shall not be made by children without sup...

Page 4: ...t blocked These may not be present in older properties however there should be enough leakage to accommodate the requirements of the Lo Carbon PureAir Home unit One method of checking this is by enter...

Page 5: ...entering the dwelling has passed through the filter first Ensure that the screw eye is attached to the beam strongly enough and that the beam is in sufficient condition to withstand the load The unit...

Page 6: ...the ceiling Fig 5 It is important not to over tighten these screws as this may warp the diffuser Fit the free end of the flexible ducting to the diffuser spigot using the worm drive clip supplied The...

Page 7: ...er spigot see Fig 7 where fitted to the unit there are locating pins that fix the heater to the unit using a bayonet fitting and the locking screw When fitted at the diffuser end make sure the directi...

Page 8: ...should be capable of disconnecting all poles having a contact separation of at least 3mm PureAir Home PureAir Home with Heater unit Ensure the local AC power supply is isolated The product has a pre w...

Page 9: ...ings will then be applied There are three buttons on the front of the unit The button is used to increase the value of a setting the button is used to reduce the value of a setting and the Mode button...

Page 10: ...ation is required optional F7 filters can be used These filters are effective at removing finer particles such as particulate emissions from diesel engines In urban areas close to main roads F7 filter...

Page 11: ...ired it is recommended not to use this setting By reducing the trickle speed threshold the fan will run at higher speed more often this would be helpful in a property with persistent damp problems Inc...

Page 12: ...y be necessary to use the manual speed selection to meet the required flow rate It is the responsibility of the installer to ensure that appropriate speeds are selected M SERVICING AND MAINTENANCE WAR...

Page 13: ...Power Input W Max Flow Rate 14 00 14 00 14 00 LWA Sound Power Level dB 35 53 35 53 35 53 Ref Flow Rate m3 s 0 04 0 04 0 04 Ref Pressure Diff Pa N A N A N A SPI W m3 h 0 09 0 09 0 09 Control Factor Co...

Page 14: ...14...

Page 15: ...15...

Page 16: ...contractor against faulty material or workmanship In the event of any part being found to be defective the product will be repaired or at the Company s option replaced without charge provided that the...

Reviews: