Installation
Kinetic MVHR Installation & Commissioning
12
4. N.B. SEE “WALL MOUNTING” on pages 14
to 16 for information on marking out the wall
for the position of the condensate drain and
wall mounting brackets.
Fit Vertical discharge 32mm waste pipe
(fitted with 22 / 32mm reducer).
Fit a ‘U’ bend condensate drain having a
minimum of a 60mm water seal or a HepvO
valve to the building’s foul water drainage
system and ensure there is a minimum 3
degree fall to allow condensate drainage.
5.
Fit the 180 degree bend supplied to a
22mm diameter x 280mm long condensate
pipe with worm drive clip.
6.
Fit pipe assembly into waste pipe and secure
90 deg elbow to condensate spigot with worm
drive clip.