Vent-Axia HR300RW6 Operating, Installation And Servicing Instructions Download Page 6

3.0 Installation

6

3.1

Controllers

1. The 

HR

300RW6 unit can be installed in

conjunction with a number of controllers.

VCON6:

The VCON6 controller can be used to

provide Off/Low/Normal/Boost/Sensor control.

(The HS6 humidistat or TIM2 over-run timer can

be used in conjunction with the VCON6 controller

to provide automatic control.

VCON5:

The VCON5 controller can be used to

provide variable speed control.

HS6:

The HS6 is a humidity sensor for switching

between HIGH and LOW speeds during the

daytime according to relative humidity levels.

TIM2:

The TIM2 is an overrun timer which can

also be used to control the 

HR

100 unit via a light

switch or remote sensor e.g. PIR detector.

3.2

Initial Preparation

1. Select an approved electrical control

arrangement for the 

HR

300RW6 unit (above).

2. After considering the site requirements 

(Section 2.0), select a suitable site for the unit

and controllers and work out the cable runs.

WARNING:

Before deciding on the final position

for the unit, check there are no buried cables,

pipes or obstructions on the outside wall.

Cable requirements:

Suitably (Basec or Har)

approved three core cable of appropriate current

carrying capacity.

3. Install the cable runs and appropriate

controllers in conjunction with a fused connection

unit. Contact gap must not be less than 3mm.

4. Choose suitable locations and install internal

louvre grilles into desired locations.

5. Connect ducting to louvre grilles and run to the

desired location of unit.

4. Working from the inside, mark out the 

position of the mounting hole - 280mm wide x

380mm high (see Fixing Template).

5. Carefully cut the holes in the inner and outer

brick courses to form a suitable aperture to

receive the unit. Ensure that this is level.

NOTE:

Bricks will cut more easily and

accurately if a series of holes are drilled close

together along the marked lines.

6. Remove the connection spigot plate, heat

exchanger, from the unit (Fig. 4).

Heat Exchanger

Fig. 4

Connection Spigot Plate

Summary of Contents for HR300RW6

Page 1: ...HR300RW6 Semi Remote Wall Mounted Heat Recovery Ventilator Installation and Servicing Instructions Please leave these instructions with the user...

Page 2: ...2...

Page 3: ...3 1 0 Introduction 4 2 0 Site Requirements 5 3 0 Installation 6 4 0 Electrical 8 5 0 Maintenance 9 Section Page Contents...

Page 4: ...esh intake airflow This provides up to 70 heat recovery from the stale extracted air 1 2 Ancillary Equipment 1 The HR300RW6 unit can be used in conjunction with a range of ancillary equipment Controll...

Page 5: ...xceed 40 C 8 Do not site the appliance in the vicinity of excessive levels of airborne oil or grease 9 If the unit is installed in a room containing a fuel burning appliance the installer must ensure...

Page 6: ...controllers and work out the cable runs WARNING Before deciding on the final position for the unit check there are no buried cables pipes or obstructions on the outside wall Cable requirements Suitabl...

Page 7: ...lace with the two fixing screws provided NOTE Ensure the fixings DO NOT inhibit removal or replacement of the heat exchanger 5 Make good around the case 6 Fit the bezel on the inside to cover the maki...

Page 8: ...cket and connect incoming wires to the appropriate terminals Figs 7 8 4 Replace plug into socket 5 Slide the heat exchanger into the unit Fig 9 6 Locate the connection spigot plate on to the front of...

Page 9: ...connection spigot plate Fig 10 4 Slide out the heat exchanger Fig 10 The heat exchanger should be washed in warm soapy water and dry thoroughly 5 Reassemble in reverse order ensuring the heat exchang...

Page 10: ...6 0 Notes 10...

Page 11: ...11...

Page 12: ...Vent Axia Ltd Fleming Way Crawley West Sussex RH10 9YX www vent axia com Comp No 372561 Iss B 0405...

Reviews: