11.0 Fault Finding
START
Before starting FAULT FINDING
carry out preliminary electrical systems checks
i.e. Earth Continuity, Polarity, Short Circuit
and Resistance to Earth.
Ensure all external controls are operating
and are set to normal running. Ensure that
a mains electrical supply is available to the
unit.
Refer to diagrams below to
identify terminals on components
(e.g. A1, D3 etc).
YES
NO
Note 1
Electricity supply must be
isolated and Fan Motor
temperature must be less than
100˚ to allow thermal trip to
reset.
Note 2
Electricity supply must be
isolated and Overheat
temperature must be less
than 80˚ to allow Overheat
Thermostat to reset.
WARNING
If the Overheat sensor or Fan
thermal trip has operated,
check the entire system and
unit for correct installation.
Check all ducting outside &
terminals for blockages.
IMPORTANT
When investigating
overheating allow the unit to
run long enough for any fault
to become apparent.
1
2
3
4
5
6
Controller
Connector
Block
C.Hood
Plug
Fan
Plug
D
E
3
2
1
G
F
B
A
C
1
2
1
2
1
2
3
O
B
C
L
N
Fuse
(3.15AT)
WHC0035A
Ensure the Cooker
Hood is closed.
Ensure continuity
between terminals
D5 & A1
and between
D6 & A2.
Check mains
supply.
Is there
mains voltage
across terminals
A1/A2?
YES
NO
Investigate cause
and
rectify fault
Replace fuse
3.15AT
Is the
fuse on the
controller
O.K.
YES
NO
Disconnect wires
from terminals
F1, F2 & F3.
Ensure voltage
selector wire is
correctly engaged.
Replace controller
Replace
cooker hood
Is the
voltage across
terminals B1 &
B2 between 80v
& 160v?
NO
Is the voltage
across F1 & B2
between 80v
& 160v?
YES
NO
See Fan Fault
Finding Chart
Check external
control wiring.
Refer to 205 wiring
diagram (section 7)
Reconnect wires
to terminals
F1, F2 & F3.
Rectify fault on
cooker hood
plug and lead.
Disconnect 4 pin
cooker hood plug.
Are both fans
operating?
YES
NO
Is the
voltage across
the blue & white
wires on the cooker hood
plug between
80v and
160v.
YES
L
N
160
140
120
100
80
Voltage Selector Wire
HR205 - Main Unit Fault Finding Chart