Inbuilt Threshold Humidistat with Rapid Rise Detection (HT models only) 

The HT models include a digital humidity sensor with pre-set Threshold and 
Rapid Rise sensing. The settings are fixed and cannot be adjusted.  
 
Threshold: 
The fan will increase in speed proportionally between trickle and boost flow rates 
at 75%RH and 85%RH.  

 

0-75%RH  

= trickle speed flow rate 

 

76-85%RH   = Proportional between trickle and boost 

 

86-100%RH   = Boost speed flow rate 

Rapid Rise Detection: 
If the humidity increases by more than 5%RH (RH2) compared to the humidity 5 
minutes ago (RH1), the fan enters boost mode. Once the humidity starts to fall, 
the fan will remain in boost for a further 30 minutes or until the humidity reaches 
the original (RH1) humidity level, whichever is sooner. 

 

D. SERVICING AND MAINTENANCE. 

 

WARNING: THE FAN AND ANCILLARY CONTROL EQUIPMENT 
MUST BE ISOLATED FROM THE POWER SUPPLY DURING 
MAINTENANCE. 

 
1.  At intervals appropriate to the installation, the fan should be inspected and 

cleaned to ensure there is no build-up of dirt or other deposits.  

2.  Wipe the inlets and front face with a damp cloth until clean.

 

 

 

The fan has sealed for life bearings, which do not require lubrication.

  

 

 
 
 
 
 

 
 

 

 

 
 
 

 

 
 
 
 
 

 

Fig.1

 Continuous trickle (no manual boost).  (The fan is internally fused) 

220-240V ~ 50Hz 

 

 

Fan 

Switched Spur 

Summary of Contents for 498095

Page 1: ...ring Instructions Stock Ref N 498095 NBR dMEV C 100 T 498096 NBR dMEV C 100 HT 498097 NBR dMEV C 125 T 498098 NBR dMEV C 125 HT PLEASE READ INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS PLEASE SAVE T...

Page 2: ...that the mains supply Voltage Frequency and Phase complies with the rating label D The Fan should only be used in conjunction with the appropriate Vent Axia products E The fan should only be used in c...

Page 3: ...ise sensing 498095 NBR dMEV C 100 T 100mm continuously running dMEV fan with fixed Timer 498096 NBR dMEV C 100 HT 100mm continuously running dMEV fan with Humidity sensor and fixed Timer 498097 NBR dM...

Page 4: ...arly draining onto the building structure plasterboard and or the fan Horizontal ducts should be arranged to slope slightly downwards away from the Fan EXTERIOR WALL MOUNTING 1 For wall mounting cut a...

Page 5: ...Fig 1 2 or 3 3 Check all connections have been made correctly 4 Ensure the impeller rotates and is free from obstructions C SETUP Installation Settings Dip Switch 1 SW1 default OFF This determines the...

Page 6: ...ducing any nuisance noise until after the user has left the room When the LS is deactivated fan will run at boost mode for the length of time the LS was present up to a maximum of 20 minutes plus the...

Page 7: ...y 5 minutes ago RH1 the fan enters boost mode Once the humidity starts to fall the fan will remain in boost for a further 30 minutes or until the humidity reaches the original RH1 humidity level which...

Page 8: ...fused 1 Rotate grille counter clockwise 2 Remove tile cover Fig 2 Continuous boost with no trickle facility The fan is internally fused 220 240V 50Hz Switched Spur Fan 3 Pole Isolator Switch Fan Lamp...

Page 9: ...e inner grille forward off the fan Mounting fixing Mounting fixing Mounting fixing Wiring terminals 220 240VAC 50Hz Rear cable entry Side cable entry cut plastic side wall to access Speed Adjustment D...

Page 10: ...0 13 12 14 45 12 16 15 15 50 14 17 16 17 55 14 19 17 18 60 15 21 18 20 65 16 22 19 21 70 17 24 21 22 75 18 25 21 23 80 18 26 22 24 85 19 26 22 24 90 20 26 23 26 95 Speed Limited in Wall Mode Setting S...

Page 11: ......

Page 12: ...or 7 years from date of purchase against faulty material or workmanship In the event of any part being found to be defective the product will be repaired or at the Company s option replaced without ch...

Reviews: