Speed Selection 

The trickle flow rate can be quickly adjusted via the dial as shown 

– either with the 

inner grille on or off (see below images). The 10-100% scale relates to a flow rate 
of  between  5-16l/s.  The  scale  is  adjusted  based  on  the  installation  type  (

SW1

). 

The boost speed is proportionally higher than the trickle flow rate. 

 

Inner grille on: 

 

 

 

 

Inner grille removed: 

 
 
Overrun Timer with Comfort mode  
(Always enabled except for the first 5 minutes of mains power)*  

The comfort mode feature offsets/delays the boost when the LS has been activated 
(e.g. from switching the light on) until after the LS has been deactivated (up to a 
maximum  of  20  minutes).  Therefore  reducing  any  nuisance  noise  until  after  the 
user has left the room.   
 
When the LS is deactivated, fan will run at boost mode for the length of time the 
LS  was  present  (up  to  a  maximum  of  20  minutes)  plus  the  standard  15  minute 
overrun time. 
 
If  the  LS  was  activated  for  less  than  3  minutes,  no  boost  will  occur  to  prevent 
nuisance activations. 
If the LS is still connected after 20 minutes, the fan will boost anyway. Once the 
LS  is  disconnected,  the  fan  will  run  for  only  20  minutes  plus  the  15min  overrun 
timeout.  
 
The  humidity  sensor  overrides  this  if  humidity  is  detected.  The  fan  will  run  as 
described for the Humidity function.  
 
*Comfort mode/overrun timer is disabled for the first 5 minutes the fan is powered 
– to allow easy testing/checking of the LS signal from the light/other switch after 
installation. After the first 5 minutes, the fan will function normally.  

 

 

 
 
 
 

Summary of Contents for 498095

Page 1: ...ring Instructions Stock Ref N 498095 NBR dMEV C 100 T 498096 NBR dMEV C 100 HT 498097 NBR dMEV C 125 T 498098 NBR dMEV C 125 HT PLEASE READ INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS PLEASE SAVE T...

Page 2: ...that the mains supply Voltage Frequency and Phase complies with the rating label D The Fan should only be used in conjunction with the appropriate Vent Axia products E The fan should only be used in c...

Page 3: ...ise sensing 498095 NBR dMEV C 100 T 100mm continuously running dMEV fan with fixed Timer 498096 NBR dMEV C 100 HT 100mm continuously running dMEV fan with Humidity sensor and fixed Timer 498097 NBR dM...

Page 4: ...arly draining onto the building structure plasterboard and or the fan Horizontal ducts should be arranged to slope slightly downwards away from the Fan EXTERIOR WALL MOUNTING 1 For wall mounting cut a...

Page 5: ...Fig 1 2 or 3 3 Check all connections have been made correctly 4 Ensure the impeller rotates and is free from obstructions C SETUP Installation Settings Dip Switch 1 SW1 default OFF This determines the...

Page 6: ...ducing any nuisance noise until after the user has left the room When the LS is deactivated fan will run at boost mode for the length of time the LS was present up to a maximum of 20 minutes plus the...

Page 7: ...y 5 minutes ago RH1 the fan enters boost mode Once the humidity starts to fall the fan will remain in boost for a further 30 minutes or until the humidity reaches the original RH1 humidity level which...

Page 8: ...fused 1 Rotate grille counter clockwise 2 Remove tile cover Fig 2 Continuous boost with no trickle facility The fan is internally fused 220 240V 50Hz Switched Spur Fan 3 Pole Isolator Switch Fan Lamp...

Page 9: ...e inner grille forward off the fan Mounting fixing Mounting fixing Mounting fixing Wiring terminals 220 240VAC 50Hz Rear cable entry Side cable entry cut plastic side wall to access Speed Adjustment D...

Page 10: ...0 13 12 14 45 12 16 15 15 50 14 17 16 17 55 14 19 17 18 60 15 21 18 20 65 16 22 19 21 70 17 24 21 22 75 18 25 21 23 80 18 26 22 24 85 19 26 22 24 90 20 26 23 26 95 Speed Limited in Wall Mode Setting S...

Page 11: ......

Page 12: ...or 7 years from date of purchase against faulty material or workmanship In the event of any part being found to be defective the product will be repaired or at the Company s option replaced without ch...

Reviews: