background image

Rear Panel Connections

When the ACC-TSENWIFI type  is configured to be a supply 

or return air temperature sensor, the sample rate is once 
every 20 seconds. External power (24Vac) is required to 

support this sampling rate.

If 24Vac is not supplied to the rear terminals of the sensor  
and 4 AA batteries are installed, the sampling rate of the  

sensor will default to once a minute.

Specifications

Operational Temperature
•  with alkaline batteries:  0° F - 120° F
•  with lithium batteries:  -20° F - 130° F

Expected Battery Life
•  Sample rate of 1 per minute:  > 1 year

Sensor Type
•  10K Ohm thermistor, 2 wire pigtail

24Vac

Included 

10K Ohm 

Sensor

HVAC Duct

sensor

gasket

wall

fig. 4

fig. 5

Figure 4 illustrates the optional 

use of an external sensor along 

with external power.

AC POWER IN

24V
AC

REMOTE

SENSOR

fig. 5

When mounting outdoors:
·  Install gasket as shown between wall and sensor
·  Keep out of direct sunlight
·  Keep out of direct rain
An ideal mounting location would be in a covered 

outdoor patio or protected by an awning or eave 

from the elements.
Use the included screw to secure the cover  

to the sensor.

Summary of Contents for ACC-TSENWIFI

Page 1: ...nsor with to understand its capabilities and pairing procedure This sensor is compatible with allVenstarWi Fi thermostats that contain the latest firmware Please consultVenstar com for a complete listing of compatible thermostats Note This sensor must be connected to the same local network as the thermostat s that will use the sensor data Configurator app icon fig 1 AC POWER IN 24VAC REMOTE SENSOR...

Page 2: ... Select Wireless Sensors 7 Select Add New Sensor 3 Install 4 AA batteries with the polarity as indicated on the ACC TSENWIFI housing see fig 3 Disregard the battery installation when 24Vac is connected to the sensor a Alkaline batteries are acceptable for operation in the temperature range of 0 F to 120 F b When operating between 20 F to 130 F it is recommended to use good quality Lithium AA batte...

Page 3: ...aline batteries 0 F 120 F with lithium batteries 20 F 130 F Expected Battery Life Sample rate of 1 per minute 1 year Sensor Type 10K Ohm thermistor 2 wire pigtail 24Vac Included 10K Ohm Sensor HVAC Duct sensor gasket wall fig 4 fig 5 Figure 4 illustrates the optional use of an external sensor along with external power fig 5 When mounting outdoors Install gasket as shown between wall and sensor Kee...

Page 4: ...nce isotrope rayonnée équivalente PIRE ne est pas plus de ce qui est nécessaire pour une communication réussie We Venstar declare under our sole responsibility that the device to which this declaration relates Complies with Part 15 of the FCC Rules Operation is subject to the following two conditions 1 this device may not cause harmful interference and 2 this device must accept any interference re...

Reviews: