This procedure allows the installer to verify that all modes of operation are fully functional.
During the verification of a main control, make sure that all optional remote controls are inactive.
11. Overall Verification
Set the slider
Set dehumidistat
Results expected
switch to
dial to
fan speed / damper
1
OFF
maximum counterclockwise
motor off / closed
2
OFF
maximum clockwise
motor off / closed
3
MIN.
maximum counterclockwise
low speed / open
4
MIN.
maximum clockwise
high speed / open
5
MAX.
maximum counterclockwise
high speed / open
6
MAX.
maximum clockwise
high speed / open
VC0010
VENTA
At its very start-up, the Altitude wall control will perform a booting sequence before
being ready to operate. The booting sequence is done when the hour display is flashing.
Refer to the installation sheet included with the Altitude wall control for more details in
programming and setting preferences.
VC0101
SMART
SET
MODE
PREF
ALTITUDE
D
EHUMIDISTAT
:
Turn dial to the maximum
clockwise position (20%).
Result expected:
Motor speed changes to high.
60-
MINUTE
CRANK
TIMER
:
Activate the timer.
Results expected:
Motor speed: High for up to
60 minutes.
11.2 O
PTIONAL
C
ONTROLS
First, turn OFF the main control device before checking the remote optional controls.
20/40/60-
MINUTE
PUSH
-
BUTTON
TIMER
:
Activate the push-button. Within
2 seconds, push one time for
20 minutes, two times for
40 minutes or three times for a
60-minute activation.
Results expected:
1.
Motor speed: High for 20, 40
or 60 minutes.
2.
Indicator light goes “ON” and
flashes every 5 seconds (one
time to indicate a 20-minute operation, two times
for a 40-minute, and three times for a
60-minute operation).
NOTE: To stop activation, push one more time.
VC0007
20 min.
40 min.
60 min.
OFF
10
20
30
40
50
60