MA-AL-T135-01-02 Manual TUL135 eng rev2 

 

   Rev.2 Page 2 of 4 

Alarm threshold of the battery internal resistance 

1 ohm 

Tension of intervention of the protection from overtensions 

18Vdc 

Dry-contact relay output for mains absence and failure 

25 Vac or 60Vdc 1A max 

 

Chart. 2 

MECHANICAL SPECIFICATIONS 

Size in mm. 

Height 373; length 310; depth 170 

Weight 

8,5  Kilos 

 

Chart. 3 

ENVIRONMENTAL SPECIFICATIONS 

Operating temperature 

From 

– 10°C to +40°C 

Humidity  

From  5% to 93% ±2% 

Cooling 

For convection 

Installation site 

In repaired position 

 

Chart. 4 

FUSES 

F1 

Fuse of the 230 Vac supplying input (T2 AL 250V) 

F5 

Fuse related to output OUT 2 (T3,15 AL 250V) 

F3 

Battery fuse (T6,3 AL 250V) 

F6 

Fuse related to output OUT3 (T3,15 AL 250V) 

F4 

Fuse related to output OUT 1 (T3,15 AL 250V) 

F8 

Fuse of protection over-voltage (T6,3 AL 250V) 

 
 

Security instructions 

 

-  For  mains  input  and  DC  outputs  +  alarms,  use  separate  holes  on  the  bottom  of  the  box  to  pass  the  cables.  Furthermore,  the 

material of the joint pipe/box must have a flammability class V-1 or better  

The relay contacts “POWER-SUPPLY FAILURE” “BATTERY FAILURE” and “MAINS MISSING” must be connected only to 
circuits operating with SELV voltage. 

-  For AC supplying, provide a 6 A protection bi-pole magneto-dynamic switch, easy to access. 
-  The wires must have a section of 1,5 mm and be equipped with adequate buttonholes where they are subject to 

pressure contact. 

-  The installation of the power supply must be carried out by qualified personnel aware of the security standards EN60950 and 

concerning power supplies CEI-64-8. 

 

INSTALLATION 

 
 

Mechanical Mounting 

 

This  device  has  to  be  mounted  on  vertical  stable  walls,  suitable  to  support  the  power  supply,  by  means  of  4  6  mm  wall  plugs,  four 
spacers and screws on the 4 holes on the bottom of the box.

 

 

Electrical connections 

 

Connect the power supply to the mains 230 Vac by use of bi-pole 6 A magneto-thermic switch (minimum distance between contacts 3 
mm) aimed to protect the line from possible short-circuits and to protect the operator from current losses towards ground. 
 

IMPORTANT:  

 

use  different  cable-passes  and  pipes  for  ac  supplying input  (mains 230 Vac) and dc o alarms (SELV). Use 

the stripes to keep cables separated inside the power supply.  

 

Tighten the three cables connected to the mains terminal by use a stripe, paying attention to fix the stripe as close as 

possible to the terminal board. 

 
The minimum section recommended for ground connection is 1,5 mm. 

For connections refer to figures Fig.4 and Fig.5. In these pictures the following important steps are shown: 

 

Chart. 5 

Output terminal board (power supply) 

BAT + 

Positive pole of the battery 

OUT 2 + 

Positive output towards charge 2 

BAT - 

Negative pole of the battery 

OUT 2 - 

Negative output towards charge 2 

OUT 1 + 

Positive output towards charge 1 

OUT 3 + 

Positive output towards charge 3 

OUT 1 - 

Negative output towards charge 1 

OUT 3 - 

Negative output towards charge 3  

 

Terminal board Alternated Supplying 

 

connection to line ( 230 Vac) 

      

     Protection ground connection  

 

N  

connection to neutral 

Controls and Adjustments 

 

The parameters shown below (P1 and P2) are adjusted at factory and 

must in no way be altered by the operator. 

Tampering of these parameters automatically means the lost of the warranty. 

 

P1  

Potentiometer for adjustment of the output voltage      --    

P2   

Potentiometer for adjustment of the output current limit.  

 

Summary of Contents for TUL 135

Page 1: ... battery internal resistance is carried out every 90 minutes if the internal resistance happens to be over 1 ohm there will be a BATTERY FAILURE It will then be necessary to replace the battery and check that terminals and fuses have a good electrical contact When the battery is replaced having mains presence the test of the internal resistance is repeated within 5 minutes A microcontroller system...

Page 2: ...ounting This device has to be mounted on vertical stable walls suitable to support the power supply by means of 4 6 mm wall plugs four spacers and screws on the 4 holes on the bottom of the box Electrical connections Connect the power supply to the mains 230 Vac by use of bi pole 6 A magneto thermic switch minimum distance between contacts 3 mm aimed to protect the line from possible short circuit...

Page 3: ... 1 Ω Start of the system even if not imperative the following sequence of connection is suggested 1 Connect mains and ground to the concerned terminal J1 The charge Led flashes and after about 30 seconds the missing battery Led flashes 2 Connect the battery After 20 seconds the Led switches off 3 Connect the charges the Leds indicating the current supplied light up SERVICING Periodical programmed ...

Page 4: ...3 BATTERY INTERRUPTED ON FIX FUSE F8 MAINS INTERRUPTED OFF NONE OF PREVIOUS FAILURES CURRENT SUPPLIED LED I 0 5A 0 5A I 1A 1A I 1 5A 1 5A I 2A 2A I 2 5A 2 5A I 3A 3A I 3 5A 3 5A I 4A 4 5A I 5A OVERCHARGED I 5A DL7 DL6 DL5 LEGEND LED OFF SLOW FLASHING 1Hz NORMAL FLASHING 2Hz QUICK FLASHING 4Hz LED ON FIX Via del Lavoro 10 30030 Salzano VE Tel 39 041 5740374 Fax 39 041 5740388 Web site www venitem c...

Reviews: