LED
on =
No Anomaly
Chart 5: Sounds DIP 4, 5, 6
Sound priority: Attention! The input priority is (5), (7) and lastly (9).
This means that if all the input are connected simultaneously to 0V (with DIP 7 and DIP 8 ON), the sound
starts (5).
Table 8: Anomalies
Chart 4: System status LED Function
DIP 3
Function
OFF
System Status LEDs Off
ON
System Status LEDs On if no anomalies
Chart 3: Alarm timing
DIP 1
DIP 2
ALARM TIMING
OFF
OFF
INFINITE
ON
OFF
3 MINUTES
OFF
ON
8 MINUTES
ON
ON
15 MINUTES
DIP 4
DIP 5
DIP 6
Terminal (5)
Terminal (7)
Terminal (9)
Current from
the battery
OFF
OFF
OFF
DIN33 descending
NFS32 Double tone
ISO8021 - 3 pause
1.700mA
ON
OFF
OFF
DIN33 descending
NFS32 Double tone
ISO8021 - 3 pause
1.000mA
OFF
OFF
ON
BS5839 Double tone
NEN2575 Asc pause
Continuous
1.800mA
ON
OFF
ON
BS5839 Double tone
NEN2575 Asc pause
Continuous
1.200mA
OFF
ON
OFF
Continuous 610Hz
Pulsed 610Hz
Two tones 610Hz – 490Hz
900mA
OFF
ON
ON
Bell-type 1.200Hz
Pulsed 610Hz
Two tones 610Hz – 490Hz
700mA
Chart 6: DIP 7 trigger polarity
DIP7
Polarity
OFF
Positive trigger (+12V or +24V)
ON
Negative trigger (0V)
Chart 7: DIP 8 Trigger type
DIP8
Change
OFF
Missing trigger
ON
Giving trigger
Anomalies
LED LD1
Relay contact
terminals 3 e 4
Speaker interruption
(test every 10s)
1 FLASH
OPEN
Recharge current is missing (V recharge < 12V)
(test every 10s)
2 FLASHES
OPEN
Disconnected battery (test every 4 hours)
3 FLASHES
OPEN
Low voltage battery (V battery < 10,5V)
(test every 10s)
4 FLASHES
OPEN
Deteriorated battery – resistance higher than 2,5 Ohm
(test every 4 hours)
5 FLASHES
OPEN
No anomalies
OFF
CLOSED
1KOhm
LED Anomaly Connection
Synchronism Connection
LD1
ANOMALY
LED