2019.10
5 / 21
Figure 2.1. VENCO Energy Recovery Units
Heat Recovery units as standard consist of five different parts as described; Exhaust Fan, Supply Fan, Fresh
Air Filter, Exhaust Air Filter, Plate Type Heat Recovery Exchanger.
Figure 2.2. VENCO Energy Recovery Units Schema
3. TECHNICAL SPECIFICATION for ENERGY RECOVERY UNITS
Technical specifications, which are valid for the heat recovery units as standard manufactured by VENCO, are
given in the table below.
Table 3.1. Technical Specifications for VHR ER Models
MODEL
VHR
ER 01
VHR
ER 04
VHR
ER 06
VHR
ER 08
VHR
ER 15
VHR
ER 28
VHR
ER 35
VHR
ER 40
VHR
ER 51
VHR
ER 54
Air Flow 0 Pa*
m³/h
143
356
629
808
1544
2789
3583
3980
5200
5387
Air Flow 150 Pa*
m³/h
-
204
413
611
1235
2248
2968
3400
3863
4325
Efficiency
%
Efficiency up to 70%, depending on working conditions
E
L
E
CT
RIC
A
L
Voltage
230Volt / 50Hz
Power
Watt
52
104
204
204
450
1100
1100
1100
1100
1100
SFP**
-
1,7
1,58
1,06
1,31
1,76
1,33
1,16
1,37
1,23
Air Filter
G3 Synthetic Filter
– For Exhaust and Fresh Air
*External static pressure
**According to EN 13779