c. Repeat step 5b. for subsequent fans until all
fans in the chain are connected in series.
d. Follow the “Fan Networking” instructions on
page 11 to complete network setup for the fans.
With Optional 1,000 ft. Bulk Spool of CAT-5e Cable
Included Component:
• 1,000 ft. Bulk Spool of CAT-5e Control Cable (1)
• Shielded, Pass-Through RJ45 Connectors (25)
Hardware/Tools Needed (Not Included):
• Fan Control (1, optional)
• CAT-5e Termination Tool
1. Determine required length of CAT-5e cable run.
Unspool appropriate amount of cable and cut to
length.
IMPORTANT:
Individual CAT-5e cable lengths must
not exceed 200 ft. in order to prevent network
communication issues.
2. Strip and remove 2 in. of CAT-5e cable jacket
leaving the foil shield intact.
3. Fold foil shield back over cable jacket and trim foil
so that 1/4 in. remains.
4. Untwist conductor pairs, straighten and align wires
according to EIA/TIA T568B wiring pinout.
1 2 3 4 5 6 7 8
1. White/Orange
2. Orange
3. White/Green
4. Blue
5. White/Blue
6. Green
7. White/Brown
8. Brown
Foil Shield
5. Trim conductor ends flush leaving 1 in. exposed.
6. Fully insert cable into shielded, pass-through RJ45
connectors until foil enters back end of connector.
Use only the provided RJ45 connectors.
7. Verify that conductors are in the correct wiring
scheme order.
8. Crimp RJ45 connector with CAT-5e termination tool
(not included).
9. Repeat on opposite end of CAT-5e cable to
complete cable construction.
10. Follow the “With Pre-Built CAT-5e Cable”
instructions on page 18 to complete
communication wiring and fan control installation.
Power Wiring Installation
DANGER
Always disconnect, lock and tag power source before
installing or servicing. Failure to disconnect power
source can result in fire, shock or serious injury.
DANGER
Pour écarter les risques d’incendie, de choc électrique
ou de blessure grave, veiller à toujours débrancher,
verrouiller et étiqueter la source de courant avant
l’installation ou l’entretien.
IMPORTANT:
Do not connect power until mechanical
installation, fire alarm relay installation, communication
wiring and fan control installation are complete.
IMPORTANT:
Do not apply power to the fan above
the rated voltage of the variable frequency drive (VFD).
Failure to comply with this warning will result in voiding
of the product warranty and may result in permanent
damage to the VFD and motor.
IMPORTANT:
To prevent electrical failures, source
power must comply with the following power quality
requirements. If source power falls outside of these
specified tolerances, an external power line filter will be
required (by others). If other power quality issues are
present, contact the factory for support.
Allowable Voltage
Fluctuation
+/- 10% of nominal
Allowable Frequency
Fluctuation
+/- 5% of nominal (47-63 Hz)
Area of Use
Do not install fans in electrical environments
with Pollution higher than Degree 2 in
accordance with UL 61800-5-1
Surge Immunity
Do not install fans in electrical environments
above Installation Class 3 in accordance
with IEC 61000-4-5
Hardware/Tools Needed (Not Included):
• Phillips Screwdriver
With Optional Electrical Plug
1. If the fan is supplied with the optional electrical
plug for power wiring, refer to the chart below for
the corresponding receptacle that will be needed
(provided by others).
Electrical Plug Reference (Locking)
Voltage
Phase
Plug*
Receptacle
208-230
1
L6-30P
L6-30R
277
1
L7-30P
L7-30R
208-230
3
L15-30P
L15-30R
460
3
L16-30P
L16-30R
*
NOTE:
Plugs are available from manufacturer. Receptacles must be
provided by others.
2. Install the receptacle according to all national and
local codes for electrical wiring.
High Volume, Low Speed Ceiling Fans