Round Fire and Combination Fire Smoke Dampers

5

Retainer Plate

Duct Connection

Area

2 in.

AIRFLOW

6 in. max.

TW

Sleeve Length

6 in. max.

Do not place retainer

plate in this groove

2 in.

Duct connection

area

Clearance for expansion

Retainer plate

Blade latch

Access door to be on

same side as blade latch

Figure 6: DFDR/FDR/SEDFDR/SSDFDR/SSFDR

3.375 IN.

FUSIBLE 
LINK
LOCATION

CLEARANCE FOR
EXPANSION

TOP VIEW OF DAMPER

6 IN. MAX

SLEEVE LENGTH

TW

DUCT 
CONNECTION
AREA

AIRFLOW

1.50 IN.

ACTUATOR

16.00 IN MAX

OPTIONAL BLADE POSITION

INDICATOR AND/OR ELECTRIC

LINK.

DUCT 
CONNECTION
AREA

2.00 IN.

1.50 IN.

Optional
Second
Retaining
Plate

Do not place retainer
plate in this groove

Figure 5: FSDR/SEFSDR/SSFSDR

Inserting Damper into Wall/Floor Openings

Insert the damper assembly into the prepared opening, to appropriate depth (see 

Figure 5 & 6

).

Special attention must be paid to ensure the following:

 

1)   The 

CL

 

(centerline) of the damper frame remains within the plane of 

the wall or floor

  2)  The sleeve does not extend more than 16 in. (406mm) beyond the wall or floor on the actuator side of the 

damper and 6 in. (152mm) on the side opposite the actuator. The sleeve may also extend up to 16 in. (406mm) 
beyond the wall or floor if the damper has an access door.

Summary of Contents for DFDR Series

Page 1: ...eiving and Handling Upon receiving dampers check for both obvious and hidden damage If damage is found record all necessary information on the bill of lading and file a claim with the final carrier Ch...

Page 2: ...terials include but are not limited to a Mortar dust b Drywall dust c Firesafing materials d Wall texture e Paint overspray 7 Damper should be sufficiently covered as to prevent overspray if wall text...

Page 3: ...rs must meet the requirements of the appropriate wall design See UL Fire Resistance Directory and or local codes Figure 1 12 in 24 in o c Maximum Floor Runner 2 in Ceiling Runner 2 Panhead Screws 24 i...

Page 4: ...assembly to allow for this expansion The wall floor opening must be a minimum of 7 8 in 22mm larger than the outside diameter of the damper Clearances Required Between Damper Sleeves and Wall Floor O...

Page 5: ...ITION INDICATOR AND OR ELECTRIC LINK DUCT CONNECTION AREA 2 00 IN 1 50 IN Optional Second Retaining Plate Do not place retainer plate in this groove Figure 5 FSDR SEFSDR SSFSDR Inserting Damper into W...

Page 6: ...p for easy installation when the clamping screw is loosened If necessary remove the clamping screw and nut see Figure 7 Position the retaining plate between the blade axle and the actuator shaft as sh...

Page 7: ...ensor with the lower temperature setting can be bypassed by an external contact closure allowing the damper to reopen until the secondary temperature is reached the sensor with the higher temperature...

Page 8: ...he latest editions of NFPA 80 90A 92 101 105 UL864 AMCA 503 03 and local codes Actuator manufacturer recommendations Damper Troubleshooting The following is a possible cause and correction list for co...

Reviews: