TUO Wi-Fi RF Chronothermostat with humidistat User Manual

DEVICE RESET

Perform a reset to delete the settings entered and restore the device to the factory 
values (excluding the network settings for remote control which can be changed as 
described on pages 52-53). 

To reset:
  1. from the initial screen, press and hold the key   to enter the configuration menu.  
   The CLOCK indication flashes.
  2. press and hold down the keys   and   simultaneously until "

RES

   appears on the display.
  3. when the display shows all the segments, keep the key   pressed until 
   "

DEF

" appears

SET

3s

SET

3s

3"

+

Initial screen

Configuration

menu

Operation mode

heating

(winter)

Regulation type

on/off 

Differential (on/off)

0.3 °C

Band (proportional)

0.5 °C

Period (proportional)

10 minutes

Adjustment command

rF (via RF signal) 

Antifreeze temperature OFF

6 °C

MEV

always active

Adj. ADJ temperature

0 °C

Min. settable temperature

2 °C

Max. adjustable temperature

50 °C

Hour meter operation   /

0 h

Automatic summer time change

active 

(according to EU rules)

Backlighting

active

Key lock password

disabled

 

To reset if the key lock is active and you do not know the unlock password, you  

      must remove and restore power and, when the display shows all the segments,  
      keep the key   pressed until "

DEF

"appears.

Summary of Contents for Tuo Wi-Fi RF Bianco

Page 1: ...Cronoumidostato Digitale TUO Wi Fi RF Manuale d Uso User Manual DIGITAL CHRONOTHERMOSTAT WITH HUMIDISTAT PDF...

Page 2: ......

Page 3: ...e Page 71 parameters for the regulation type Page 71 antifreeze temperature Page 72 adjustment of the measured temperature Page 72 Wi Fi connection configuration Page 73 system control mode air condit...

Page 4: ...It s necessary to connect the device and then install the appropriate app on your smartphone or tablet available free for iOS and Android devices The colour of the display backlighting can be chosen b...

Page 5: ...essibility to the connection terminals without appropriate tools must be guaranteed 4 The device must be installed and activated in compliance with current electric systems standards 5 Before accessin...

Page 6: ...the Vemer Cloud in progress Connection to the active Wi Fi network Measured relative humidity Configuration menu RF radiofrequency connection configuration with actuator ADV advanced parameters of th...

Page 7: ...49 TUO Wi Fi RF Chronothermostat with humidistat User Manual CONNECTION DIAGRAM L N NC NA C AIR CONDITIONER or BOILER DEHUMIDIFIER MEV Note the boiler or air conditioner can also be controlled via th...

Page 8: ...tains or in positions with excess or total lack of ventilation to avoid that the reading of the temperature measured by the probe is in some way offset Device installation Connection and association w...

Page 9: ...e following 1 Install and start the Clima Wi Fi app on your smartphone or tablet 2 Choose Register and fill in the e mail and password fields Note for security reasons it is recommended to choose a pa...

Page 10: ...the app and the device 5 Now choose the Wi Fi network to connect the device to and enter the password be careful to digit faithfully all characters uppercase lowercase spaces digits that compose them...

Page 11: ...tion between the app and the device 5 Now enter the complete name of the Wi Fi network where connect the device and enter the password be careful to digit faithfully all characters uppercase lowercase...

Page 12: ...can control your TUO Wi Fi RF device remotely easily and intuitively Access using the access credentials email password chosen during registration phase of your account identifies a device or created...

Page 13: ...cates that the program can not be modified or canceled This screen shows the TUO Wi Fi RF status indicates the measured temperature and humidity 23 1 C 45 7 RH the operating mode Heating the system st...

Page 14: ...the three available tempe rature T1 T2 and T3 marked by blue green and red colours Created a program for a day it s possible to copy it to any other day of the week Copy function It is also possible...

Page 15: ...fy the icon that identifies it set the themperature values TO T1 T2 and T3 NOTE the chronothermostat is compatible with Google Home and Amazon Echo By the association with Google or Amazon account is...

Page 16: ...mperature blocking local operation choosing the time zone enter the user email who will receive the alarm set themperature thresholds and delay to trigger the alarm NOTE LOCAL OPERATION When the chron...

Page 17: ...set by the user Manual mode It allows you to use the device as a thermostat and the regulation is according to the temperature Tm Off mode It is suitable when long periods of absence are expected In t...

Page 18: ...ation Off operation 3 3 To switch from manual to automatic operation To switch from automatic operation or manual to the one switched off and vice versa Manual operation Tmoperation Automatic operatio...

Page 19: ...allows you to set date and time It also allows the configuration of the daylight saving time change The RF menu allows configuration and the radiofrequency connection test between the device and the...

Page 20: ...ice acquires the date and time settings from the server and no settings are required However if you need to manually set the date and time values proceed as follows To exit the date and time setting p...

Page 21: ...symbol the summer time change winter time is identified by the symbol For example in Italy the summer time starts the last LST Sunday 7 of March 03 at 2 00 o clock and the last LST Sunday 7 of October...

Page 22: ...program for one or more days of the week modify one or more existing programs by personalizing the profile that is assigning different temperature levels for one or more hours of the day How to choos...

Page 23: ...es independent for every hour of the day The switching delay for programming the MEV follows a similar behavior How to customize the profile of a Px program starting from midnight 00 00 press the keys...

Page 24: ...es T1 5 C T2 15 C T3 18 C heating winter operation T1 off T2 23 C T3 25 C conditioning summer operation How to change the temperature values T1 T2 T3 To exit the temperature change press the key once...

Page 25: ...ew point In particular when the measured humidity is lower than the HR1 threshold the dehumidifier is always off while the air conditioner is on if the measured temperature is above the setpoint when...

Page 26: ...MEV programming for day Y Initial screen Menu configuration Menu EXT Choose the day Y Choose on off for the selected time Choose on off for the next hour SET 3s x4 times After choosing day Y press the...

Page 27: ...Timed automatic set a timing during the automatic operation to maintain this operation until the timing has elapsed At the end of the timing the device activates the off operation Off timed set a tim...

Page 28: ...proposed in sequence Press the keys and to change the value of the selected parameter the key to go to the next parameter the key to exit and confirm the changes Note the device exits the menu after...

Page 29: ...to modify this parameter only in case of real need For more information on the characteristics of the on off and proportional regulation logic see Regulation type on page 81 Parameters for the regulat...

Page 30: ...etting excludes the antifreeze function in this case when the device is off no minimum temperature is guaranteed Adjustment of the measured temperature In particular installation conditions it can hap...

Page 31: ...with a Vemer account flashing not associated with any Vemer account Note during the first 20 seconds or so of this screen viewing the icon is always flashing The MAC address of the device is a sequen...

Page 32: ...vice and the air conditioner or the boiler Setting up rf to choose the radiofrequency control reL to select the relay control Factory value rf radiofrequency Note the configuration and the test of the...

Page 33: ...C ki Factory value 2 C ki is the upper limit Allowed values L0 50 C Factory value 50 C Password for key lock Under particular installation conditions for example in public buildings hotels etc it may...

Page 34: ...resumes the count from 0h Display backlighting The display backlighting can be off blue after pressing a key fixed of a colour that can be chosen among 48 variants variable based on the difference be...

Page 35: ...ehumidifier and the controlled mechanical ventilation unit RF MENU CONNECTION CONFIGURATIONWITHTHEACTUATORS Initial screen Configuration menu SET 3s Activate configuration or test RF menu x7 times Cho...

Page 36: ...are paired 3s During normal operation sending the commands to the actuators is indicated by the lighting of the RF message It is possible to repeat the procedure described above to combine multiple r...

Page 37: ...Minimum values resetting 3 Keypad unlock When the key lock is active the device adjusts the temperature using the set programming In this condition after pressing a key the display shows the writing B...

Page 38: ...the segments keep the key pressed until DEF appears SET 3s SET 3s 3 Initial screen Configuration menu Operationmode heating winter Regulationtype on off Differential on off 0 3 C Band proportional 0 5...

Page 39: ...n mind that a low differential 0 1 C 0 2 C leads as a consequence more frequent ignitions of the system but the temperature will be more uniform than a high value 0 9 C 1 C Proportional regulation onl...

Page 40: ...o make the ThermoPro RF valve work by opening modulation In this way the valve opens proportionally according to the difference between the set temperature set point and the detected temperature Selec...

Page 41: ...and PIN serial number If it is necessary to assign control of the device to another user typical situation for example when the device is installed in a rented house and the tenants change proceed as...

Page 42: ...10 RH centered on the setpoint Operating mode heating winter or conditioning summer Configurable display backlighting Automatic winter time summer time Keypad lock with password for installation in p...

Page 43: ...ctrical and electronic equipment WEEE If the crossed out bin symbol appears on the equipment or packaging this means the product must not be included with other general waste at the end of its working...

Page 44: ...19 20 21 22 23 P3 T3 T2 T1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 P4 T3 T2 T1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 P5 T3 T2 T1 0 1 2 3 4 5 6 7 8 9 10 1...

Page 45: ...19 20 21 22 23 P3 T3 T2 T1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 P4 T3 T2 T1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 P5 T3 T2 T1 0 1 2 3 4 5 6 7 8 9 10 1...

Page 46: ......

Page 47: ......

Page 48: ...V3IS01009 100 202302 Vemer S p A I 32032 Feltre BL Via Camp Lonc 16 e mail info vemer it web site www vemer it 02 2023...

Reviews: