TUO GSM Chronothermostat User Manual

Set the operating mode

Use the following commands to set automatic, manual or off operation:

CRONO ON AUTOMATIC

 

[timing] [d/h]

 

CRONO ON MANUAL

 [timing] [d/h]

 

CRONO OFF

 

[timing] [d/h]

[timing]

 and 

[d/h] 

are optional parameters. When not specified, the set status is main-

tained until further command.

[timing] 

 is a numeric value from 1 to 99 

[d/h]

  is the unit of measurement: 

G

 

= days

H

 

=

 

hours

The description of the timings and their operation is shown on page. 67.

For example:

CRONO ON AUTOMATIC: sets the automatic operation 

CRONO AUTOMATIC ON 20 H: sets the automatic operation for 20 hours, after which 
the operation will be switched off

CRONO OFF 2 D: sets the operation off for 2 days, after which the automatic or manual 
operation is activated (depending on which was the operation set before activating off 
operation).

Set the operating mode

To configure the device for heating (winter) or air conditioning (summer) use the 
commands:

CRONO HEATING 

CRONO COOLING

Summary of Contents for TUO GSM VE771800

Page 1: ...Digital Chronothermostat TUO GSM User Manual...

Page 2: ......

Page 3: ...68 operating mode Pagina 68 Type of regulation Pagina 69 parameters for regulation type Pagina 69 antifreeze temperature Pagina 70 adjustment of the measured temperature Pagina 70 GSM connection confi...

Page 4: ...terpreted by the device only if the sender number is saved in the device address book or if they are accompanied by the SMS protection password Every time the device receives a valid command after exe...

Page 5: ...to the connection terminals without appropriate tools must be guaranteed 4 The device must be installed and activated in compliance with current electric systems standards 5 Before accessing the conne...

Page 6: ...Each hour is associated with one of the 3 temperatures Temperature T1 Temperature T2 Temperature T3 h Active timed operation Receiving a command in progress Connection to the active GSM network Measu...

Page 7: ...Manual CONNECTION DIAGRAM L N NC NO C L N L N NO C NC NO C NC U U L N L N NO C NC NO C NC U U Connection diagram for the control of the boiler heat pumps etc Connection diagram for the supply of circu...

Page 8: ...rature conditions of the entire environment Make sure the area is covered by the GSM signal to guarantee a stable communication In this regard the device allows verifying the intensity of the signal o...

Page 9: ...intensity operator identifier signal intensity progressive operator 3 press the keys and to scan the detected telephone operators and display the intensity of each one The device displays the signals...

Page 10: ...rs saved in your phonebook On pages from 49 to 58 is described the procedure to memorize one or more numbers in the phonebook of TUO GSM and the commands to be sent to control it GENERAL NOTES A comma...

Page 11: ...nebook by call or by SMS command However the first number in the phonebook must be memorized via a telephone call following the procedure described below Store the first number in the phonebook 1 go t...

Page 12: ...her numbers as well At the end press the key twice to exit the GSM screen Store the other numbers via SMS Send the command to the device PHONEBOOK index number index is the position of the phonebook w...

Page 13: ...asurement G days H hours The description of the timings and their operation is shown on page 67 For example CRONO ON AUTOMATIC sets the automatic operation CRONO AUTOMATIC ON 20 H sets the automatic o...

Page 14: ...is set no minimum temperature is guaranteed with the consequent risk of system freezing Set the temperature Tm manual mode To set the temperature value Tm use the following command Tm value value is...

Page 15: ...cessary to communicate to the device the number of the inserted SIM card using the command CRONO NUMBER number number is the number of the SIM card inserted inside TUO GSM In this case the device upon...

Page 16: ...set operating mode current temperature used as setpoint relay status presence of the power supply GSM signal coverage SIM card number in the device CRONO INFO CRONO INFO ALL use the commands CRONO INF...

Page 17: ...M INT threshold hysteresis delay threshold is the temperature value below which an alarm is considered hysteresis is the value used to calculate the condition of re entry from the alarm When the measu...

Page 18: ...message to the numbers saved in the phonebook in position 1 2 and 3 SEND ALARM POWER 1 when a power failure occurs it sends a message to the number saved in the phonebook in position 1 Note a new reci...

Page 19: ...sends a message to signal the approaching of the expiration or the exhaustion of the credit By default the setting requires these messages to be redirected to the number saved in position 1 of the ph...

Page 20: ...d in the phonebook It is recommended to change the password to ensure greater protection To change the password use the command PASSWORD new password new password is a 4 digit number For example PASSW...

Page 21: ...ce adjusts the temperature based on the value of T2 from 00 00 to 6 00 and from 8 00 to 17 00 T3 from 6 00 to 8 00 and from 17 00 to 21 00 T1 from 21 00 to 24 00 The values of T1 T2 and T3 can be set...

Page 22: ...eration 3 3 To switch from manual to automatic operation To switch from automatic operation or manual to the one switched off and vice versa Manual operation Tm operation Automatic operation Manual op...

Page 23: ...the automatic operation T1 T2 T3 The TIMER menu allows setting of one of the 3 timed operations The PROG menu allows you to change the programming of the automatic operating mode The ADV menu allows...

Page 24: ...clock menu to set the date and time and to configure time change from summer time to winter time and vice versa To exit the date and time setting press the key once to return to the configuration menu...

Page 25: ...symbol the summer time change winter time is identified by the symbol For example in Italy the summer time starts the last LST Sunday 7 of March 03 at 2 00 o clock and the last LST Sunday 7 of October...

Page 26: ...e or more days of the week modify one or more existing programs by personalizing the profile that is assigning different temperature levels for one or more hours of the day How to choose a different p...

Page 27: ...delays of 15 30 45 minutes independent for every hour of the day How to customize the profile of a Px program starting from midnight 00 00 press the keys and to assign to each hour of the day one of...

Page 28: ...2 15 C T3 18 C heating winter operation T1 off T2 23 C T3 25 C conditioning summer operation How to change the temperature values T1 T2 T3 To exit the temperatures change press the key once to return...

Page 29: ...automatic set a timing during the automatic operation to maintain this operation until the timing has elapsed At the end of the timing the device activates the off operation Off timed set a timing dur...

Page 30: ...in sequence Press the keys and to change the value of the selected parameter the key to go to the next parameter the key to exit and confirm the changes Note the device exits the menu after about 40...

Page 31: ...n the characteristics of the on off and proportional regulation logic see Regulation types on page 76 Parameters for the regulation type this menu varies depending on the chosen regulation type If the...

Page 32: ...udes the antifreeze function in this case when the device is off no minimum temperature is guaranteed Adjustment of the measured temperature In particular installation conditions it can happen that th...

Page 33: ...tal available 4 the indication of the type of error in case it is present a malfunction 5 From this menu it is also possible to check if a phone number is present in the phonebook and possibly in whic...

Page 34: ...ory value 2 C ki is the upper limit Allowed values L0 50 C Factory value 50 C Password for key lock Under particular installation conditions for example in public buildings hotels etc it may be necess...

Page 35: ...essing a key fixed of a colour that can be chosen among 48 variants variable based on the difference between the measured temperature and the set temperature blue when the measured temperature is lowe...

Page 36: ...ty value measured by the probe with a resolution of 0 1 RH Humidity regulation is not possible Keypad unlock When the key lock is active the device adjusts the temperature using the set programming In...

Page 37: ...pressed until DEF appears SET 3s SET 3s 3 Initial screen Configuration menu To reset if the key lock is active and you do not know the unlock password you must remove and restore power and when the di...

Page 38: ...t a low differential 0 1 C 0 2 C leads as a consequence more frequent ignitions of the system but the temperature will be more uniform than a high value 0 9 C 1 C Proportional regulation only for oper...

Page 39: ...scale 0 C 50 C Measured and displayed temperature resolution 0 1 C Temperature regulation range 2 0 C 50 C Measurement update every 20 seconds Measurement accuracy 0 5 C Temperature regulation on off...

Page 40: ...2 23 P3 T3 T2 T1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 P4 T3 T2 T1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 P5 T3 T2 T1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14...

Page 41: ...2 23 P3 T3 T2 T1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 P4 T3 T2 T1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 P5 T3 T2 T1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14...

Page 42: ...English 80 TUO GSM Chronothermostat User Manual...

Page 43: ......