SET MENU - TEMPERATURES T1, T2, T3 SETTING
Initial screen
Configuration menu
SET Menu
Change T1
Change T2
Change T3
SET
3s
x2 times
Access the SET menu to change the values of the 3 temperatures used in automatic
operation. The factory setting includes:
• T1 = 15°C, T2 = 18°C, T3 = 21°C (heating/winter operation )
• T1 = off, T2 = 23°C, T3 = 25°C (conditioning/summer operation )
How to change the temperature values T1/ T2/ T3
To exit the temperature change:
• press the key once to return to the configuration menu
• press the key twice to exit the menu and return to the initial screen
Note: temperature values between
L0
(minimum value)
and
kI
(maximum value) are allowed.
These factory values are:
L0
= 2°C,
kI
= 50°C but can be modified through the ADV
menu.
Note: the condition T1 ≤ T2 ≤ T3 must be respected.