        Quick Setup 

           

VEM motors Thurm GmbH                                                    

Compact Drives Series M21 ... T

                  

10/2005

 

 

   

2

 

 

 
You may use unshielded cable for connecting the mains terminals. The phases of the mains supply 
and the earth have to connect to the referring terminals. Cable inlet have to put through one of the 
3 cable glands. 
 
Sizes of cable glands:  

P = 0,55 up to 3 kW:   

 

3 x M20x1.5;  

     

P = 4 up to 7,5 kW:    

 

2 x M20x1.5; 1 x M25x1.5 

 

Tightening torques:   

L1, L2, L3:  

0,55 up to 4 kW:  

0,5 ... 0,6 Nm 

 

 

 

 

 

 

5 up to 7,5 kW:  

1,2 ... 1,5 Nm   

 

 

 

 

Earth Screw (at any powers): 

3,4 Nm 

 

 

 

 

Cover screws (at any powers ):  

2,2 ... 2,4 Nm 

 
Prefuses max.: 

 

P = 0,55 up to 3 kW:   

 

16 A

 

   

 

 

 

P = 4 up to 7,5 kW:   

 

25 A 

 
Protecting equipment: 

Use ELCB relays of type B with leakage currents of 100mA 
(ELCB relays of type A are not allowed for direct current content (DC) 
in the fault current and power-up with short charging current to earth) 

 
1.2. 

Terminals for data communication and control signals 

 

 

Communication to the Compact Drive is realized via terminal block X100. Drive control is possible 
via terminal block X101.  
For information on terminal blocks X100 and X101, please see 

table A and B

 

X100: Terminal block for data communication   

 

 

 

Table A 

 

Terminal No. 

Function 

 

P RS 485 

For connection to 

N RS 485 

Bus or PC 

5 V DC 

Supply for 

0 V DC 

RS 485  bus 

 
 

X101: Terminal block for analog/digital control signals  

 

 

Table B 

 

Terminal No. 

Function 

Example 

Analog input(0 ... 20 mA) 

 

  

Analog (0 ... 10 V)-/digital input 2 

Speed reference 

Digital input (or pulse) 3 

Reset 

Digital input (or precise stop) 4 

Start 

Digital input (other) 5  

Start + Reversing 

24 V DC supply for digital inputs (max. 150 mA)   

10 V DC supply for potentiometer (max. 15 mA)   

0 V for terminals 1 ... 7 and 9 

 

Analog output (0 ... 20 mA)/ 
Digital output (24V/ 25 mA) 

Trip indication 
 

 

 

 

 

 

 

 

 

 

 

 

 

X102: Terminal block for relay output 

 

 

 

 

 

Table C 

 

Terminal No. 

Function 

1-2 

Make (normally open) 

1-3 

Break (normally closed) 