Quick Setup
VEM motors Thurm GmbH
Compact Drives Series M21 ... T
10/2005
2
You may use unshielded cable for connecting the mains terminals. The phases of the mains supply
and the earth have to connect to the referring terminals. Cable inlet have to put through one of the
3 cable glands.
Sizes of cable glands:
P = 0,55 up to 3 kW:
3 x M20x1.5;
P = 4 up to 7,5 kW:
2 x M20x1.5; 1 x M25x1.5
Tightening torques:
L1, L2, L3:
0,55 up to 4 kW:
0,5 ... 0,6 Nm
5 up to 7,5 kW:
1,2 ... 1,5 Nm
Earth Screw (at any powers):
3,4 Nm
Cover screws (at any powers ):
2,2 ... 2,4 Nm
Prefuses max.:
P = 0,55 up to 3 kW:
16 A
P = 4 up to 7,5 kW:
25 A
Protecting equipment:
Use ELCB relays of type B with leakage currents of 100mA
(ELCB relays of type A are not allowed for direct current content (DC)
in the fault current and power-up with short charging current to earth)
1.2.
Terminals for data communication and control signals
Communication to the Compact Drive is realized via terminal block X100. Drive control is possible
via terminal block X101.
For information on terminal blocks X100 and X101, please see
table A and B
.
X100: Terminal block for data communication
Table A
Terminal No.
Function
1
P RS 485
For connection to
2
N RS 485
Bus or PC
3
5 V DC
Supply for
4
0 V DC
RS 485 bus
X101: Terminal block for analog/digital control signals
Table B
Terminal No.
Function
Example
1
Analog input(0 ... 20 mA)
2
Analog (0 ... 10 V)-/digital input 2
Speed reference
3
Digital input (or pulse) 3
Reset
4
Digital input (or precise stop) 4
Start
5
Digital input (other) 5
Start + Reversing
6
24 V DC supply for digital inputs (max. 150 mA)
7
10 V DC supply for potentiometer (max. 15 mA)
8
0 V for terminals 1 ... 7 and 9
9
Analog output (0 ... 20 mA)/
Digital output (24V/ 25 mA)
Trip indication
X102: Terminal block for relay output
Table C
Terminal No.
Function
1-2
Make (normally open)
1-3
Break (normally closed)