VDOT-ASD-100 Aspiration Detector
Velocity Detection
6
VDOT-ASD-100 Aspirating Smoke Detector User’s Manual V1
Alarm Levels and Time Delay
-
Alert (0~60 sec.)
-
Action (0~60 sec.)
-
Fire-1 (0~60 sec.)
-
Fire-2 (0~60 sec.)
Environment Smoke Learning
-
24hours, 365days Non-Stop Smoke Background Level Learning
Flow Detection
-
Detection Principle: Heat Mass Detection
-
Pipe Flow Normalize to 100%
-
Flow High and Flow Low Fault
-
Adjustable Flow Detection Sensitivity
-
Adjustable Flow Fault Threshold
Relay Output
-
7 Relays on Termination Board (Configurable)
-
Rating: 2A@30 VDC
General Purpose Inputs
-
4xGPIs (Configurable)
-
GPI Functions: RESET/ISOLATE/SILENCE/TEST/MAINS FAULT/BATT. FAULT/POWER
FAULT/SENSITIVITY MODE 1/SENSITIVITY MODE 2/SCAN/UDI-1/UDI-2/UDI-4/UDI-5
*Note: UDI, User Defined Input
Communication
-
RS-485 Network
-
Maximum number of devices on Network: 250
-
Built in repeater
-
Maximum cable length between two adjacent devices: 1.2km
-
Support Modbus RTU open protocol
Control
-
<Reset>, <Isolate>, <Silence> & <Test> buttons
Display