VDOT-ASD-100 Aspiration Detector
Velocity Detection
20
VDOT-ASD-100 Aspirating Smoke Detector User’s Manual V1
and is disabled by default. To enable the GPI-2, mount both the P1 and P2 jumper selection
to 2/3 PIN and set the corresponding GPI function. When the external active input is
disconnected for less than 3 seconds, the corresponding GPI-2 function is activated, and
when the GPI-2 connection line is disconnected or open for more than 6 seconds, the GPI-2
fault is reported.
o
RS-485
l
Two RS-485 Terminals
l
Built in RS-485 repeater, the cable length can be extended to next device for
another 1.2km.
l
RS-485 Network can be configured in closed loop for better communication
reliability. The communication can switch direction to communicate with devices
behind the failure point when there’s device failure, line break or line short circuit.
l
Computer Management System (a computer software) can monitor all devices on
network.
l
SCADA/HMI/PLC systems capable of Modbus RTU open protocol can communicate
with ASD devices.
VDOT-NET64 Velocity Aspirating Network Configuration
D+
D-
S
D+
D-
S
D+
D-
S
D+
D-
S
偵測主機
D+
D-
S
D+
D-
S
D+
D-
S
D+
D-
S
偵測主機
偵測主機
偵測主機
D+
D-
S
D+
D-
S
D+
D-
S
D+
D-
S
偵測主機
D+
D-
S
D+
D-
S
D+
D-
S
D+
D-
S
偵測主機
偵測主機
偵測主機
AVA 通訊網路RS-485 連線架構
AVA 最大不超過250元件
24AWG-2P
單/雙隔離網接地線
ASD-Device
24AWG Twisted Paired
Screened Cable
Closed Loop Con
ASD-Device
ASD-Device
ASD-Device
ASD-Device
ASD-Device
ASD-Device
ASD-Device
Maximum 250 devices
on one network